| Plan Review Notes For Permit 22100607 |
| Permit Number |
22100607 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-04-24 13:05:55 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | | | 1. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE | | | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO | | | WALL CONNECTIONS WILL BE IMPROVED/REVISED SUBMITTED | | | ENGINEER???S STRUCTURAL INVESTIGATION LETTER TO PROVIDE | | | EXISTING ROOF-TO-WALL LOAD PATH CONNECTION ANALYSIS | | | SHOWING COMPLIANCE WITH WIND LOADS IN TABLE 706.8.1 & | | | VALIDATED BY A LICENSED FLORIDA DESIGN PROFESSIONAL. | | | SECOND REQUEST. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|