Plan Review Notes
Plan Review Notes For Permit 22100603
Permit Number 22100603
Review Stop M
Sequence Number 2
Notes
Date Text
2022-12-13 07:55:302ND REVIEW FMC
 PERMIT: 22100603
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NEW MECHANICAL SHEET ADDED WITHOUT SUBMITTING THE
 OLD SHEET OR PROVIDING A MASTER PERMIT NUMBER FOR THE
 PROJECT. PLEASE PROVIDE THE MASTER PERMIT NUMBER FOR
 THE PROJECT SO THE REVIEWER CAN COMPARE WHAT HAS
 CHANGED. FBC 107.3.5
  
 2) THE VALUE CANNOT BE LEFT BLANK ON THE PLAN REVIEW
 REQUEST FORM. THE VALUE FOR THE WORK MUST BE GIVEN.
  
 3) THE NEW M-1 SHEET STATES THE REVISION IS FOR
 CHANGING DAMAGED DUCTWORK IN THE DINING ROOM. PROVIDE
 THE DUCTWORK ON THE DRAWING INCLUDING THE SIZE OF THE
 DAMAGED AND NEW DUCTWORK. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  