Plan Review Notes
Plan Review Notes For Permit 22100569
Permit Number 22100569
Review Stop G
Sequence Number 2
Notes
Date Text
2022-12-21 07:36:312ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 THIS REVIEW GOES ALONG WITH REVISION 22090996
  
 1. ----
  
 2. COMMENT NOT ADDRESSED ---
 2017 WPB AMENDS 107.2.1 - THE GENERATOR YOU'VE ADDED
 SHOWS A BTU VALUE OF 10K. A 10K BTU GENERATOR SEEMS
 UNUSUAL. CAN YOU PLEASE SHOW ME THE SPECIFICATIONS FOR
 THE GENERATOR.
  
 3. COMMENT NOT ADDRESSED ---
 PLEASE ADDRESS COMMENTS ON REVISION 22090996 AS WELL.
  
 4. 2020 FRC G2413.3 (402.3) - YOU'VE SUPPLIED A SIZING
 CHART THAT IS FOR CSST, BUT THE GAS LINE IS POLY. ALSO,
 THAT CHART IS A 5 PSI CHART WITH A 3.5 PSI DROP, WHICH
 IS NOT HEARD OF IN RESIDENTIAL. PLEASE SHOW THE YOU ARE
 GOING TO HAVE A 5 PSI METER BY SUBMITTING A LETTER FROM
 FPU. ALSO, ON YOUR DRAWING, YOU'VE SHOWN THE LINE FOR
 THE 221K LOAD AT .5 PSI. THE SIZING IS OFF. THE LOADS
 ARE OFF. TANKLESS WATER HEATERS ARE LIMITED TO 199K
 BTU. TOO MANY INACCURACIES TO REVIEW THIS PLAN.
  
 THIS IS NOT A COMPLETE REVIEW UNTIL THE REVISION IS
 ADDRESSED AND THE DRAWING IS CORRECTED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  