2022-11-03 13:23:271ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 912.1 HORIZONTAL WET VENT PERMITTED - THE
 TUBS NEED TO BE DISCHARGED DOWNSTREAM OF THE WET VENT
 SYSTEM. THE DOG TUBS ARE NOT BATHROOM GROUP FIXTURES
 AND SHALL DISCHARGE DOWNSTREAM OF THE WET VENT SYSTEM
 AND BE SEPARATELY VENTED.
  
 2. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWING PRINT THEIR NAME, SIGN THEIR NAME,
 AS WELL AS PUT YOUR CONTRACTOR NUMBER ON THE DRAWING AS
 REQUIRED BY THE WEST PALM BEACH AMENDMENTS TO CHAPTER
 1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  