Plan Review Notes
Plan Review Notes For Permit 22100412
Permit Number 22100412
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-10-17 15:36:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF AN EXIT STARIWAY AT THE
 PROVIDED ADDRESS BUT THERE IS NOT SITE PLAN SHOWING THE
 LOCATION AND/OR ORIENATION TO THE BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE A SITE PLAN
 SHOWING THE LOCATION OF THE STAIR.
  
  
 2) THERE IS NO INDICATION OF THE EXISTING STAIR
 DIMENSIONS.
  
 PLEASE PROVIDE THE EXISTING STAIR DIMENSIONS INDICATING
 THAT THESE NEW STAIRS MEET OR EXCEED THE EXISTING
 STAIRS.
  
 OR PROVIDE A LIFE SAFETY PLAN INDICATING THE OCCUPANCY
 LOAD OF THE 2ND FLOOR AND THAT THESE NEW STAIRS MEETS
 OR EXCEEDS THE EXITING REQUIREMENTS OF NFPA 101 CH
 12/13.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]