| Plan Review Notes For Permit 22100412 |
| Permit Number |
22100412 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-17 15:36:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF AN EXIT STARIWAY AT THE | | | PROVIDED ADDRESS BUT THERE IS NOT SITE PLAN SHOWING THE | | | LOCATION AND/OR ORIENATION TO THE BUILDING. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE A SITE PLAN | | | SHOWING THE LOCATION OF THE STAIR. | | | | | | | | | 2) THERE IS NO INDICATION OF THE EXISTING STAIR | | | DIMENSIONS. | | | | | | PLEASE PROVIDE THE EXISTING STAIR DIMENSIONS INDICATING | | | THAT THESE NEW STAIRS MEET OR EXCEED THE EXISTING | | | STAIRS. | | | | | | OR PROVIDE A LIFE SAFETY PLAN INDICATING THE OCCUPANCY | | | LOAD OF THE 2ND FLOOR AND THAT THESE NEW STAIRS MEETS | | | OR EXCEEDS THE EXITING REQUIREMENTS OF NFPA 101 CH | | | 12/13. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|