| Plan Review Notes For Permit 22100412 |
| Permit Number |
22100412 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-08 10:55:59 | STAIR REPLACEMENT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SITE PLAN SHOWING THE LOCATION OF | | | THE STAIR. | | | | | | 2) PLEASE SHOW THE HANDRAIL EXTENSION AT THE TOP TO | | | CONTINUE IN THE SAME DIRECTION AS THE STAIR (ONE SIDE | | | DOES THE OTHER SIDE IS SHOWN TURNING) FBC 1014.6 | | | HANDRAIL EXTENSIONS.THE EXTENSIONS OF HANDRAILS SHALL | | | BE IN THE SAME DIRECTION OF THE FLIGHTS OF STAIRS AT | | | STAIRWAYS AND THE RAMP RUNS AT RAMPS. | | | | | | 3) IF A WALKING PATH IS UNDER THE STAIR PLEASE SHOW | | | COMPLIANCE WITH FBC ACCESSIBILITY 307.4 VERTICAL | | | CLEARANCE. | | | VERTICAL CLEARANCE SHALL BE 80 INCHES (2030 MM) HIGH | | | MINIMUM. GUARDRAILS OR OTHER BARRIERS SHALL BE PROVIDED | | | WHERE THE VERTICAL CLEARANCE IS LESS THAN 80 INCHES | | | (2030 MM) HIGH. THE LEADING EDGE OF SUCH GUARDRAIL OR | | | BARRIER SHALL BE LOCATED 27 INCHES (685 MM) MAXIMUM | | | ABOVE THE FINISH FLOOR OR GROUND. |
|