| Plan Review Notes For Permit 22100383 |
| Permit Number |
22100383 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-14 08:35:30 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L FRANCIS, | | | FIRE INVESTIGATOR, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE PROVIDE THE SPECS FOR THE LAMINATE AND | | | UNDERLAYMENT THAT INDICATE THEY MEET THE FOLLOWING | | | QUALIFICATIONS FROM NFPA 101: | | | | | | 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN | | | THE CLASSES SPECIFIED | | | IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE | | | CRITICAL RADIANT FLUX | | | REQUIREMENTS. | | | 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.45 W/CM2, AS DETERMINED | | | BY THE TEST DESCRIBED IN 10.2.7.3. | | | 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II | | | INTERIOR FLOOR FINISH | | | SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN | | | 0.22 W/CM2, BUT LESS | | | THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN | | | 10.2.7.3. | | | | | | | | | CAITLIN L FRANCIS | | | FIRE INVESTIGATOR | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4728 | | | [email protected] |
|