| Plan Review Notes For Permit 22100359 |
| Permit Number |
22100359 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-03-02 16:02:49 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | | | 1. PROVIDE EQUIPMENT SPECIFICATION (LUMINAIRES, PUMPS). | | | FBC 107.3.5.3 | | | 2. PROVIDE ELECTRICAL INFORMATION (WIRES, CONDUITS, | | | PROTECTIONS, POWERED FROM). FBC 107.3.5.3 | | | | | | END OF COMMENTS | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | RUBEN PEREZ PERDOMO, P.E. | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6738 | | | [email protected] | | | |
|