| 2023-01-24 11:12:45 | ZONING AND PLANNING |
| | PROJECT: CIELO 840 N DIXIE HWY |
| | PERMIT NO. 22100340 |
| | DATE: JANUARY 24, 2023 |
| | CONTACT: CLAUDIA IBAVEN, CITY URBAN DESIGNER, AT |
| | 561-822-1402 OR VIA [email protected]. |
| | I HAVE REVIEWED THE ABOVE REFERENCED PETITION AND |
| | PROVIDE THE FOLLOWING COMMENTS: |
| | |
| | AS THE DESIGN CHANGED FOR THE PRIVATE OPEN SPACE |
| | COURTYARD LOCATED IN THE NORTH BUILDING, AND OTHER |
| | MINOR CHANGES ALTERED OTHER OPEN SPACE CONFIGURATIONS |
| | IN THE PROJECT, PLEASE SUBMIT THE FOLLOWING REVISED |
| | OPEN SPACE DIAGRAM SHEETS INDICATING WITH CLOUDS |
| | CHANGES FROM WHAT WAS APPROVED ON THE MASTER PERMIT NO. |
| | 21100764: |
| | - 009 SHEET A-0.3 |
| | - 050 SHEET L1-6-01 |
| | - 051 SHEET L1-6-02 |
| | |
| | SHEET A-2.1.1 NORTH BUILDING GROUND LEVEL |
| | THANK YOU FOR CLARIFYING THE CHANGE ON THE GROUND FLOOR |
| | STOREFRONT DOOR THAT WAS REPLACED WITH A WINDOW TO |
| | ACCOMMODATE MEDIATION LOUNGE. |
| | PLEASE CLARIFY IF CLOUD HIGHLIGHTING THE CORNER ON N |
| | DIXIE HWY AND EUCALYPTUS STREET AFFECTED ANY ELEVATIONS |
| | OR SITE PLAN SHEETS. |
| | |
| | SHEET A-3.1.1 |
| | WEST ELEVATION |
| | - PLEASE CLARIFY IF WINDOW???S MULLIONS BETWEEN GRIDS 9 |
| | & 11 ARE DIFFERENT FROM THE ELEVATION APPROVED IN |
| | MASTER PERMIT 21100764. |
| | |
| | NORTH ELEVATION |
| | - PLEASE CLARIFY IF WINDOW???S MULLION AT GRID N.M. ON |
| | THE 8TH FLOOR IS DIFFERENT FROM THE ELEVATION APPROVED |
| | IN MASTER PERMIT 21100764. |
| | |
| | SHEET A-3.1.3 & A-3.1.4 |
| | - REGARDING THE PICKLEBALL ENCLOSURE, PLEASE CLARIFY |
| | ANY CHANGES ON WHICH SHEETS COMPARED TO SHEETS |
| | SUBMITTED WITH MASTER PERMIT 21100764. |
| | |
| | NOTE, SHEET A-3.1.2 WAS NOT SUBMITTED, IF ANY CHANGES |
| | HAVE BEEN MADE, PLEASE SUBMIT SHEET WITH NOTING CHANGES |
| | WITH CLOUDS. |
| | |
| | OTHER COMMENTS: |
| | HAS ANY OF THE MATERIALS LISTED IN THE ELEVATION LEGEND |
| | CHANGED FROM WHAT WAS ORIGINALLY APPROVED BY DAC? |
| | PLEASE CONFIRM THAT MECHANICAL EQUIPMENT ON ROOF IS |
| | SCREENED WITH A WALL OR SCREENING AS TALL AS THE |
| | EQUIPMENT. |
| | |
| | --END OF COMMENTS-- |