| Date |
Text |
| 2023-01-04 16:23:27 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100340 |
| | 1/4/2023 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED |
| | BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION. |
| | CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW |
| | COMMENTS |
| | |
| | 1) 2ND REQUEST. SHEETS A-1.1.1 & P-2.1.1: PLUMBING |
| | FIXTURE CALCULATIONS NOT PROVIDED- TABLE 403.1 & SEC. |
| | 403.1.1. PLEASE PROVIDE A SCHEDULE THAT SHOWS THE |
| | REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE A & B |
| | OCCUPANCIES AND OCCUPANT LOADS SHOWN ON THE PLAN. IT |
| | APPEARS THE SINGLE-OCCUPANT TOILET ROOM SHOWN ON THE |
| | PLAN WITH ONE WATER CLOSET AND ONE LAVATORY MAY MEET |
| | THE REQUIRMENT HOWEVER THE REQUIRED DRINKING FOUNTAINS |
| | AND SERVICE SINK ARE NOT ACCOINTED FOR OR SHOWN ON THE |
| | PLANS. |
| | |
| | 2) 2ND REQUEST. AT A MINIMUM, PERMIT APPLICATIONS FOR |
| | THE POTABLE WATER BACKFLOW PREVENTER AND GREASE |
| | INTERCEPTOR ARE S REQUIRED FOR THE PLUMBING PLAN REVIEW |
| | TO BE APPROVED. |
| | PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE |
| | POTABLE WATER BACKFLOW PREVENTER, GREASE INTERCEPTOR, |
| | IRRIGATION, IRRIGATION BACKFLOW, AND POOL. IF REQUESTED |
| | GAS CAN ALSO BE UNDER A SEPARATE PERMIT. DUE TO A |
| | CHANGE IN PROCESS, THE BACKFLOW AND GREASE INTERCEPTOR |
| | PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL |
| | OF THE PLUMBING REVISION. YOU CAN SUBMIT AN APPLICATION |
| | TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| | SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR |
| | THE POTABLE WATER BACKFLOW PREVENTER, GREASE |
| | INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW. |
| | PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST |
| | FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB. |
| | DEPARTMENT, (561) 822-2062 OR [email protected]. |
| | |
| | 5) 2ND REQUEST. P-2.1.1 & P-6.2.1. THE DETAILS DO AND |
| | NOTES DO NOT INDICATE THE ALARMS WILL BE PROVIDED: THE |
| | ELEVATOR AND TRASH ROOM SUMP PUMPS SHALL BE EQUIPPED |
| | WITH OIL ALARMS OR THE SUMP DISCHARGE SHALL BE CONVEYED |
| | TO AN OIL SEPARATOR(S)- SEC. 1003.4 FBC P. |
| | |
| | 6) 2ND REQUEST. THE DETAIL ON P-6.1.1 SHOWS A 2-INCH |
| | CONDENSATE PIPE DISCHARGING ONTO GRADE 8-INCHES AWAY |
| | FROM THE BUILDING. THIS IS NOT AN APPROVED PLACE OF |
| | DISPOSAL PER SEC. 314.2.1. PLEASE PROVIDE PIPE |
| | CONNECTION TO STORM DRAIN OR DISCHARGE TO DRYWELL. |
| | P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE |
| | CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF |
| | DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC. |
| | 314.2.1 FBC P. |
| | |
| | |
| | 14) 2ND REQUEST TO SHOW LOCATIONS OF STORM DRAIN |
| | CLEANOUTS. P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6: |
| | PROVIDE CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE |
| | THEY EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC. |
| | 1101.8 FBC P. |
| | |
| | 18) 2ND REQUEST. THE WATER HEATER DETAILS ON P-6.1.2 |
| | ARE THE APARTMENT WATER HEATERS WHICH ARE APPROVED. |
| | PROVIDE THE GROUND FLOOR STORAGE AND TANKLESS WATER |
| | HEATER DETAILS P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE |
| | EQUIPMENT SCHEDULES AND INSTALLATION DETAILS FOR THE |
| | GROUND FLOOR WATER HEATERS SHOWN ON THE ISO- SEC. |
| | 107.2.1 WPB. THE DETAIL SHOULD SHOW THE MEANS OF |
| | LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER |
| | PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC |
| | P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A |
| | BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE |
| | MAKER- SEC. 608.3 FBC P. |
| | |
| | 19) 2ND REQUEST. P-5.1.7 & P-6.1.2: SHOW THE MEANS OF |
| | PROVIDING TEMPERED WATER DELIVERY FROM THE GROUND FLOOR |
| | LAVATORY IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE |
| | THAT TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL |
| | BE ASSE 1070 LISTED- SEC. 607.1.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |