2022-11-18 19:23:36RESIDENTIAL R(3)FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22100334
 6205 WASHINGTON RD
  
 NOTE:
 RESPONSE TO INFORMATION EMAILED BY LUKE FISHER AND
 RESPONSE LETTER FROM SAM MALO ON 11/18/22
  
  
 9- PROVIDE PRODUCT APPROVAL FOR:
  
 PREVIOUS COMMENT:
 A)INFORMATION SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL21838.3 IS FOR "INSWING" DOOR. PLANS SHOW "OUTSWING"
 DOOR. PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS.
 ALSO, NEED TO SUBMIT THE DOOR INSTALLATION
 INSTRUCTIONS.
 NOTE: PLEASE SUBMIT COMPLETE PRODUCT APPROVAL ON THE
 SAME PDF FILE, DON'T SPLIT PRODUCT APPROVAL ON
 DIFFERENT FILES.
  
 RESPONSE:
 MR/ MALO'S RESPONSE LETTER SAYS PRODUCT APPROVAL
 FL-21838.3 HAS BEEN REPLACED WITH FL-21838.4. REVISED
 PRODUCT APPROVAL FL-21838.4 WAS NOT SUBMITTED.
 NOTE: PDF ATTACHMENT SUBMITTED IN THIS EMAIL IS FOR THE
 METAL ROOF AND OWENS CORNING UNDERLAYMENT. I DIDN'T ASK
 FOR THIS. THERE ARE NO COMMENTS FOR THE METAL ROOF.
 THE COMMENT REGARDING PLEASE SUBMIT COMPLETE PRODUCT
 APPROVAL ON THE SAME PDF FILE, DON'T SPLIT PRODUCT
 APPROVAL ON DIFFERENT FILES IS TO UPLOAD A COMPLETE
 PRODUCT APPROVAL IN THE SAME PDF. FOR EXAMPLE ENTRY
 DOOR FLORIDA PRODUCT APPROVAL COVER PAGE AND
 CORRESPONDING INSTALLATION INSTRUCTIONS IN THE SAME
 PDF. NOT SEPARATING THE COVER PAGE AND THE INSTALLATION
 INSTRUCTIONS IN TWO DIFFERENT FILES. ALSO, EACH PRODUCT
 APPROVAL SHOULD BE IN ONE FILE NOT ALL PRODUCT APPROVAL
 IN THE SAME FILE.
  
 PREVIOUS COMMENT:
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES.
  
 RESPONSE:
 MR/ MALO'S RESPONSE LETTER SAYS "SIZE OF STRUCTURAL
 MULL NOTED ON PRODUCT APPROVAL, SHEET 11 OF 25".
 REVISED PRODUCT APPROVAL IDENTIFYING MULLION SIZE WAS
 NOT SUBMITTED.
  
 PREVIOUS COMMENT:
 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. COORDINATE WITH ENTRY DOOR PRODUCT APPROVAL
 COMMENT ABOVE.
  
 RESPONSE:
 MR/ MALO'S RESPONSE LETTER SAYS "EOR HAS SIGNED SHEET
 3.1, WHICH HAS UPDATED PRODUCT APPROVAL SCHEDULE,
 THEREFORE CERTIFYING HIS ACCEPTANCE". REVISED SIGNED
 AND SEALED SHEET 3.1 WAS NOT SUBMITTED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  