| 2022-11-18 19:23:36 | RESIDENTIAL R(3)FOURTH BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #22100334 |
| | 6205 WASHINGTON RD |
| | |
| | NOTE: |
| | RESPONSE TO INFORMATION EMAILED BY LUKE FISHER AND |
| | RESPONSE LETTER FROM SAM MALO ON 11/18/22 |
| | |
| | |
| | 9- PROVIDE PRODUCT APPROVAL FOR: |
| | |
| | PREVIOUS COMMENT: |
| | A)INFORMATION SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| | FL21838.3 IS FOR "INSWING" DOOR. PLANS SHOW "OUTSWING" |
| | DOOR. PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS. |
| | ALSO, NEED TO SUBMIT THE DOOR INSTALLATION |
| | INSTRUCTIONS. |
| | NOTE: PLEASE SUBMIT COMPLETE PRODUCT APPROVAL ON THE |
| | SAME PDF FILE, DON'T SPLIT PRODUCT APPROVAL ON |
| | DIFFERENT FILES. |
| | |
| | RESPONSE: |
| | MR/ MALO'S RESPONSE LETTER SAYS PRODUCT APPROVAL |
| | FL-21838.3 HAS BEEN REPLACED WITH FL-21838.4. REVISED |
| | PRODUCT APPROVAL FL-21838.4 WAS NOT SUBMITTED. |
| | NOTE: PDF ATTACHMENT SUBMITTED IN THIS EMAIL IS FOR THE |
| | METAL ROOF AND OWENS CORNING UNDERLAYMENT. I DIDN'T ASK |
| | FOR THIS. THERE ARE NO COMMENTS FOR THE METAL ROOF. |
| | THE COMMENT REGARDING PLEASE SUBMIT COMPLETE PRODUCT |
| | APPROVAL ON THE SAME PDF FILE, DON'T SPLIT PRODUCT |
| | APPROVAL ON DIFFERENT FILES IS TO UPLOAD A COMPLETE |
| | PRODUCT APPROVAL IN THE SAME PDF. FOR EXAMPLE ENTRY |
| | DOOR FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| | CORRESPONDING INSTALLATION INSTRUCTIONS IN THE SAME |
| | PDF. NOT SEPARATING THE COVER PAGE AND THE INSTALLATION |
| | INSTRUCTIONS IN TWO DIFFERENT FILES. ALSO, EACH PRODUCT |
| | APPROVAL SHOULD BE IN ONE FILE NOT ALL PRODUCT APPROVAL |
| | IN THE SAME FILE. |
| | |
| | PREVIOUS COMMENT: |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. |
| | |
| | RESPONSE: |
| | MR/ MALO'S RESPONSE LETTER SAYS "SIZE OF STRUCTURAL |
| | MULL NOTED ON PRODUCT APPROVAL, SHEET 11 OF 25". |
| | REVISED PRODUCT APPROVAL IDENTIFYING MULLION SIZE WAS |
| | NOT SUBMITTED. |
| | |
| | PREVIOUS COMMENT: |
| | 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. COORDINATE WITH ENTRY DOOR PRODUCT APPROVAL |
| | COMMENT ABOVE. |
| | |
| | RESPONSE: |
| | MR/ MALO'S RESPONSE LETTER SAYS "EOR HAS SIGNED SHEET |
| | 3.1, WHICH HAS UPDATED PRODUCT APPROVAL SCHEDULE, |
| | THEREFORE CERTIFYING HIS ACCEPTANCE". REVISED SIGNED |
| | AND SEALED SHEET 3.1 WAS NOT SUBMITTED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |