| 2022-11-14 13:03:51 | RESIDENTIAL R(3) REVISION, THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #22100334 |
| | 6205 WASHINGTON RD |
| | |
| | ORIGINAL BUILDING PROVISO: |
| | |
| | 9- PROVIDE PRODUCT APPROVAL FOR: |
| | |
| | PREVIOUS COMMENT: |
| | A)NEW DOOR ON FLORIDA PRODUCT APPROVAL FL21133.31 |
| | SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER OF RECORD. NEED PRODUCT APPROVAL THAT |
| | MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES. |
| | |
| | RESPONSE: |
| | INFORMATION SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| | FL21838.3 IS FOR "INSWING" DOOR. PLANS SHOW "OUTSWING" |
| | DOOR. PROVIDE PRODUCT APPROVAL THAT MATCHES PLANS. |
| | ALSO, NEED TO SUBMIT THE DOOR INSTALLATION |
| | INSTRUCTIONS. |
| | NOTE: PLEASE SUBMIT COMPLETE PRODUCT APPROVAL ON THE |
| | SAME PDF FILE, DON'T SPLIT PRODUCT APPROVAL ON |
| | DIFFERENT FILES. |
| | |
| | ORIGINAL COMMENT: |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. MULLION SIZE NO |
| | SPECIFIED. |
| | |
| | ORIGINAL COMMENT: |
| | 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. COORDINATE WITH ENTRY DOOR PRODUCT APPROVAL |
| | COMMENT ABOVE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |