| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3. SUBMITTED PRODUCT APPROVAL |
| | FL1654-R31 HAS BEEN REVISED TO FL1654-R32. PLEASE |
| | PROVIDE THE FOLLOWING: INCLUDE COVER PAGE, EVALUATION |
| | REPORT PAGES 1-5 AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. FLORIDA DBPR PRODUCT APPROVAL FL1654-R31 |
| | SYSTEM NO. W-196 DO NOT MEET THE MINIMUM ZONE 3 DESIGN |
| | PRESSURE REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C |
| | AREAS. PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN |
| | PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY C/PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH |
| | AN APPROVED SYSTEM. ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. |
| | 2. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| | IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| | WALL CONNECTIONS WILL BE IMPROVED. FOURTH REQUEST. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |