Plan Review Notes
Plan Review Notes For Permit 22100308
Permit Number 22100308
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-22 15:40:37ELECTRIC REVIEW FAILED
 1) IT APPEARS L PANEL SCHEDULE IS MISLABELED AS A
 120/208 PANEL AND SHOULD BE LABELED AS 480/277. PLEASE
 CORRECT AS APPLICABLE. FBC 107.2 NEC 215.5
 2) PLEASE DETAIL BY NOTE , VOICE, DATA, ACCESS CONTROL,
 SECURITY, FIRE ALRM, SIGN AND OTHER LOW VOLTAGE SYSTEM
 WIRING REQUIRE A SEPARATE PERMT
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  