| 2022-11-02 10:03:48 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.3.5.1.3/2020 FPC 403.1.1 - I AM |
| | UNABLE TO LOCATE THE FIXTURE CALCULATIONS THAT ARE |
| | REQUIRED TO BE SUBMITTED. ALSO, TO BE NOTED, YOU WILL |
| | BE REQUIRED TO HAVE SEPARATE FACILITIES UNLESS YOU MEET |
| | ONE OF THE EXCEPTIONS IN 403.2 OR YOU CAN SHOW A PATH |
| | OF TRAVEL LESS THAN 500 FEET PER 403.3.3. |
| | |
| | 2. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE |
| | LIMITING FOR HOT WATER DELIVERY. THE THERMOSTAT ON THE |
| | WATER CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR |
| | TEMPERED WATER. A MIXING DEVICE IS REQUIRED FOR THIS |
| | SECTION AND IS IN ADDITION TO THE LIMITING DEVICE |
| | REQUIRED FOR TEMPERED PUBLIC HANDWASHING. THE DEVICE |
| | MUST COMPLY WITH ASSE 1017 AND MUST BE INSTALLED AT THE |
| | HOT WATER SOURCE PER 2020 FPC 613.1. |
| | |
| | 3. 2020 FPC 403.1 - PLEASE SHOW A SERVICE SINK OR |
| | ACCESS TO ONE IN COMPLIANCE WITH THIS SECTION. |
| | |
| | 4. 2020 FPC 403.1 - PLEASE SHOW A DRINKING FOUNTAIN OR |
| | ACCESS TO ONE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |