Plan Review Notes
Plan Review Notes For Permit 22100265
Permit Number 22100265
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-02 10:03:481ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3/2020 FPC 403.1.1 - I AM
 UNABLE TO LOCATE THE FIXTURE CALCULATIONS THAT ARE
 REQUIRED TO BE SUBMITTED. ALSO, TO BE NOTED, YOU WILL
 BE REQUIRED TO HAVE SEPARATE FACILITIES UNLESS YOU MEET
 ONE OF THE EXCEPTIONS IN 403.2 OR YOU CAN SHOW A PATH
 OF TRAVEL LESS THAN 500 FEET PER 403.3.3.
  
 2. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE
 LIMITING FOR HOT WATER DELIVERY. THE THERMOSTAT ON THE
 WATER CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR
 TEMPERED WATER. A MIXING DEVICE IS REQUIRED FOR THIS
 SECTION AND IS IN ADDITION TO THE LIMITING DEVICE
 REQUIRED FOR TEMPERED PUBLIC HANDWASHING. THE DEVICE
 MUST COMPLY WITH ASSE 1017 AND MUST BE INSTALLED AT THE
 HOT WATER SOURCE PER 2020 FPC 613.1.
  
 3. 2020 FPC 403.1 - PLEASE SHOW A SERVICE SINK OR
 ACCESS TO ONE IN COMPLIANCE WITH THIS SECTION.
  
 4. 2020 FPC 403.1 - PLEASE SHOW A DRINKING FOUNTAIN OR
 ACCESS TO ONE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved