Plan Review Notes
Plan Review Notes For Permit 22100265
Permit Number 22100265
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-08 16:48:291ST REVIEW FMC
 PERMIT: 22100265
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE REQUIRED EXHAUST FAN CFM???S FOR THE
 BATHROOM CONTROLLED BY THE LIGHT SWITCH. THIS WOULD BE
 INTERMITTENT AND WOULD REQUIRE 70 CFM???S PER WATER
 CLOSET. FMC TABLE 403.3.1.1
  
 2) PROVIDE A NOTE ON THE MECHANICAL DRAWING THAT THE
 AREA ABOVE THE CEILING IS A PLENUM AND MUST COMPLY WITH
 FMC 602.2.1
  
 3) PLEASE SHOW THE WSHP CONDENSATE LINES AND THE
 TERMINATION LOCATION. FMC 307
  
 4) SHEET M3.1: THE WATER SOURCE HEAT PUMP SCHEDULE
 LISTS HP-1-20A TO HAVE AN AIR FLOW OF 540. IT IS
 UNCLEAR ON THE DRAWING IF EACH SD-3 SUPPLIES 540
 CFM???S OF AIR OR IF THE GROUP OF 3 SUPPLIES 540
 CFM???S OF AIR. THE RG-2 INDICATES 450 CFM???S OF
 RETURN AIR, AGAIN IT IS UNCLEAR IF THIS IS FOR A SINGLE
 RG-2 OR IF IT IS FOR THE GROUP OF 3 RG-2???S. THE
 OFFICE AREA SHOWS CFM???S AT EACH DIFFUSER. PLEASE
 CLEAR THIS UP AS IT WOULD MAKE A LARGE DIFFERENCE IN
 THIS DESIGN. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  