| 2022-11-08 16:48:29 | 1ST REVIEW FMC |
| | PERMIT: 22100265 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE REQUIRED EXHAUST FAN CFM???S FOR THE |
| | BATHROOM CONTROLLED BY THE LIGHT SWITCH. THIS WOULD BE |
| | INTERMITTENT AND WOULD REQUIRE 70 CFM???S PER WATER |
| | CLOSET. FMC TABLE 403.3.1.1 |
| | |
| | 2) PROVIDE A NOTE ON THE MECHANICAL DRAWING THAT THE |
| | AREA ABOVE THE CEILING IS A PLENUM AND MUST COMPLY WITH |
| | FMC 602.2.1 |
| | |
| | 3) PLEASE SHOW THE WSHP CONDENSATE LINES AND THE |
| | TERMINATION LOCATION. FMC 307 |
| | |
| | 4) SHEET M3.1: THE WATER SOURCE HEAT PUMP SCHEDULE |
| | LISTS HP-1-20A TO HAVE AN AIR FLOW OF 540. IT IS |
| | UNCLEAR ON THE DRAWING IF EACH SD-3 SUPPLIES 540 |
| | CFM???S OF AIR OR IF THE GROUP OF 3 SUPPLIES 540 |
| | CFM???S OF AIR. THE RG-2 INDICATES 450 CFM???S OF |
| | RETURN AIR, AGAIN IT IS UNCLEAR IF THIS IS FOR A SINGLE |
| | RG-2 OR IF IT IS FOR THE GROUP OF 3 RG-2???S. THE |
| | OFFICE AREA SHOWS CFM???S AT EACH DIFFUSER. PLEASE |
| | CLEAR THIS UP AS IT WOULD MAKE A LARGE DIFFERENCE IN |
| | THIS DESIGN. FBC 107.3.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |