| Plan Review Notes For Permit 22100245 |
| Permit Number |
22100245 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-11 15:43:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) A DETAILED LIFE SAFETY REVIEW COULD NOT BE COMPLETED | | | DUE TO NO PROPOSED OCCUPANCY LIFE SAFETY PLANS WERE | | | ATTACHED. | | | | | | NEW WALLS OR NEW COLUMNS MAY AFFECT PROPOSED EXTING, | | | EXIT TRAVEL PATHS AND TRAVEL DISTANCES. | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN IN THE RELATED AREAS. | | | | | | FYI - SHOULD THE LIFE SAFETY PLANS NOT BE AFFECTED AT | | | THIS TIME AND/OR WILL BE ADDRESSED ON FUTURE SUBMITTALS | | | PLEASE PROVIDE A DETAILED NOTE OF ACKNOWLEDGMENT BY THE | | | DESIGNER OR EOR. | | | | | | | | | 1A) THERE IS NO INDICATION OF WHAT IS EXISTING AND WHAT | | | IS NEW. | | | | | | FOR CLARITY, PLEASE PROVIDE DETAILS OF EXISTING AND | | | NEW. | | | | | | FYI - SHOULD THE EXISTING/NEW NOT AFFECT LIFE SAFETY | | | PLAN AT THIS TIME AND/OR WILL BE ADDRESSED ON FUTURE | | | SUBMITTALS PLEASE PROVIDE A DETAILED NOTE OF | | | ACKNOWLEDGMENT BY THE DESIGNER OR EOR. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|