| 2022-11-15 14:31:03 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS AN INDICATION OF A SURVEY; HOWEVER, THERE |
| | IS SITE PLAN INDICATING THE PROPOSED LOCATION OF THE |
| | GARAGE. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A SITE PLAN. |
| | |
| | |
| | 2) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH |
| | SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY |
| | |
| | 42.2.8 ILLUMINATION OF MEANS OF EGRESS. |
| | 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN |
| | ACCORDANCE WITH SEC TION 7.8. |
| | 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT |
| | HOURS, MEANS OF |
| | EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH |
| | WINDOWS ARRANGED TO |
| | PROVIDE THE REQUIRED LEVEL OF ILLUMINATION ON ALL |
| | PORTIONS OF THE MEANS |
| | OF EGRESS DURING SUCH HOURS, WHEN APPROVED BY THE |
| | AUTHORITY HAVING |
| | JURISDICTION |
| | |
| | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE |
| | WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE |
| | REQUIRED IN |
| | CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT ACCESS |
| | SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| | CORRIDORS, RAMPS, ESCALATORS, |
| | AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF |
| | THIS REQUIREMENT, |
| | EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, |
| | AISLES, CORRIDORS, |
| | RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO |
| | A PUBLIC WAY |
| | |
| | PLEASE PROVIDE FOR THE REQUIRED ILLUMINATION OR PROVIDE |
| | DETAILS OF THE ALTERNATIVE REQUIREMENT. |
| | |
| | |
| | 2A) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH |
| | SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY |
| | |
| | 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | PLEASE PROVIDE AN EXIT SIGN. |
| | |
| | |
| | 3) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH |
| | SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY |
| | |
| | 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| | PROVIDED IN |
| | NORMALLY OCCUPIED STORAGE OCCUPANCIES IN ACCORDANCE |
| | WITH SECTION 7.9, |
| | EXCEPT FOR SPACES OCCUPIED ONLY DURING DAYLIGHT HOURS |
| | WITH NATURAL |
| | ILLUMINATION IN ACCORDANCE WITH 42.2.8.2. |
| | |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| | ADDRESSED IN |
| | SECTION 11.7 |
| | (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| | OF THIS CODE |
| | (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| | (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| | ENCLOSURES, FOR WHICH |
| | THE FOLLOWING ALSO APPLY: |
| | (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| | INCLUDE A |
| | STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| | ENCLO SURE MECHANICAL VENTILATION EQUIPMENT. |
| | (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| | FOR THE |
| | STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| | SUPPLY. |
| | (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN |
| | ACCORDANCE |
| | WITH 7.2.1.6.2 |
| | |
| | PLEASE PROVIDE THE REQUIRED EMERGENCY LIGHTING |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH |
| | SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY |
| | |
| | 42.2.7 DISCHARGE FROM EXITS. DISCHARGE FROM EXITS SHALL |
| | BE IN ACCOR DANCE WITH SECTION 7.7 |
| | |
| | 7.7 DISCHARGE FROM EXITS |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC |
| | WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| | PROVIDED IN 7.7.1.2 |
| | THROUGH 7.7.1.4. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |