2022-11-15 14:31:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A SURVEY; HOWEVER, THERE
 IS SITE PLAN INDICATING THE PROPOSED LOCATION OF THE
 GARAGE.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A SITE PLAN.
  
  
 2) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH
 SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY
  
 42.2.8 ILLUMINATION OF MEANS OF EGRESS.
 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN
 ACCORDANCE WITH SEC TION 7.8.
 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT
 HOURS, MEANS OF
 EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH
 WINDOWS ARRANGED TO
 PROVIDE THE REQUIRED LEVEL OF ILLUMINATION ON ALL
 PORTIONS OF THE MEANS
 OF EGRESS DURING SUCH HOURS, WHEN APPROVED BY THE
 AUTHORITY HAVING
 JURISDICTION
  
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE
 WITH SECTION 7.8 FOR EVERY BUILDING AND STRUCTURE WHERE
 REQUIRED IN
 CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS
 SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,
 AND PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT,
 EXIT DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS,
 RAMPS, ESCALATORS, WALKWAYS, AND PASSAGEWAYS LEADING TO
 A PUBLIC WAY
  
 PLEASE PROVIDE FOR THE REQUIRED ILLUMINATION OR PROVIDE
 DETAILS OF THE ALTERNATIVE REQUIREMENT.
  
  
 2A) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH
 SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY
  
 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 PLEASE PROVIDE AN EXIT SIGN.
  
  
 3) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH
 SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY
  
 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN
 NORMALLY OCCUPIED STORAGE OCCUPANCIES IN ACCORDANCE
 WITH SECTION 7.9,
 EXCEPT FOR SPACES OCCUPIED ONLY DURING DAYLIGHT HOURS
 WITH NATURAL
 ILLUMINATION IN ACCORDANCE WITH 42.2.8.2.
  
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN
 SECTION 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH
 THE FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLO SURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN
 ACCORDANCE
 WITH 7.2.1.6.2
  
 PLEASE PROVIDE THE REQUIRED EMERGENCY LIGHTING
  
  
  
 4) THERE IS NO INDICATION OF THE PROPOSED OCCUPANCY
 CLASSIFICATION.
  
 IT APPEARS TO BE A COMMERCIAL PARKING GARAGE, WHICH
 SHALL COMPLY WITH NFPA 101 CH 42, STORAGE OCCUPANCY
  
 42.2.7 DISCHARGE FROM EXITS. DISCHARGE FROM EXITS SHALL
 BE IN ACCOR DANCE WITH SECTION 7.7
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  