| Plan Review Notes For Permit 22100218 |
| Permit Number |
22100218 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-01-11 09:35:17 | PLEASE ADDRESS ALL COMMENTS BELOW FROM 2ND REVIEW | | | CYCLE: | | | | | | 2ND REVIEW FMC | | | PERMIT: 22100218 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PERMIT APPLICATION HAS THE ADDRESS OF 544 | | | NORTHWOOD RD, THE DRAWING HAS THE ADDRESS OF 540 | | | NORTHWOOD RD. SUBMIT DOCUMENTS THAT ARE CONSISTENT. | | | | | | 2) THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE | | | A LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE | | | BUILDINGS IN THAT AREA TO HAVE RTU???S. PROVIDE THE | | | MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS | | | PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE | | | USE OF THIS TENANT SPACE. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|