| 2022-10-17 08:51:47 | 1ST REVIEW FMC | | | PERMIT: 22100218 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PERMIT APPLICATION NUMBERS 22100216 AND 22100218 | | | HAVE THE SAME DRAWING. SUBMIT DRAWINGS THAT PERTAIN TO | | | THE WORK BEING PERFORMED UNDER THE PERMIT SUBMITTED FOR | | | EACH ADDRESS. | | | | | | 2) PROVIDE THE COMPLETED LIKE FOR LIKE CHANGE OUT FORMS | | | FOR THE CHANGE OUTS ON BOTH AHU???S. IT APPEARS THAT | | | THE UNITS ARE LOCATED ON THE ROOF. A LIKE FOR LIKE | | | WOULD MEAN THE NEW UNITS WOULD ALSO BE RTU???S. IF THIS | | | IS NOT A LIKE FOR LIKE CHANGE OUT PROVIDE EQUIPMENT | | | SIZING CALCULATIONS FOR EACH UNIT. | | | | | | 3) SHOW THE OUTSIDE AIR CALCULATIONS FOR EACH TENANT | | | SPACE. FMC 403.3.1.1 | | | | | | 4) DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR | | | NAME. THE DRAWING MUST ALSO INCLUDE THE ADDRESS. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|