Plan Review Notes
Plan Review Notes For Permit 22100218
Permit Number 22100218
Review Stop M
Sequence Number 1
Notes
Date Text
2022-10-17 08:51:471ST REVIEW FMC
 PERMIT: 22100218
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PERMIT APPLICATION NUMBERS 22100216 AND 22100218
 HAVE THE SAME DRAWING. SUBMIT DRAWINGS THAT PERTAIN TO
 THE WORK BEING PERFORMED UNDER THE PERMIT SUBMITTED FOR
 EACH ADDRESS.
  
 2) PROVIDE THE COMPLETED LIKE FOR LIKE CHANGE OUT FORMS
 FOR THE CHANGE OUTS ON BOTH AHU???S. IT APPEARS THAT
 THE UNITS ARE LOCATED ON THE ROOF. A LIKE FOR LIKE
 WOULD MEAN THE NEW UNITS WOULD ALSO BE RTU???S. IF THIS
 IS NOT A LIKE FOR LIKE CHANGE OUT PROVIDE EQUIPMENT
 SIZING CALCULATIONS FOR EACH UNIT.
  
 3) SHOW THE OUTSIDE AIR CALCULATIONS FOR EACH TENANT
 SPACE. FMC 403.3.1.1
  
 4) DESIGNER OF THIS DRAWING MUST PRINT AND SIGN THEIR
 NAME. THE DRAWING MUST ALSO INCLUDE THE ADDRESS. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  