| Plan Review Notes For Permit 22100217 |
| Permit Number |
22100217 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-14 15:09:53 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE CEILING HEIGHT - FBC 1208.2 | | | | | | 2) THE DOOR SCHEDULE SHOWS THE FRONT DOOR AND THE | | | RESTROOM DOOR TO BE THE SAME - GLASS DOORS - PLEASE | | | CLARIFY. | | | | | | 3) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS | | | "REFLECTIVE SURFACE" WHEN REFERRING TO THE DIMENSION | | | FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC 603.3 | | | MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 4) ACCESSIBLE RESTROOM = THE CLEAR FLOOR SPACE FOR THE | | | INSWING DOOR IS SHOWN ON TOP OF THE TOILET - SHOULD BE | | | CLEAR FLOOR SPACE - FBC 603.2.3 (2) WHERE THE TOILET | | | ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE AND A CLEAR | | | FLOOR SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE | | | ROOM BEYOND THE ARC OF THE DOOR SWING, DOORS SHALL BE | | | PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OR | | | CLEARANCE REQUIRED FOR ANY FIXTURE. | | | | | | 5) ACCESSIBLE RESTROOM = PLEASE SHOW THE DOOR | | | MANEUVERING CLEARANCE TO EXIT THE RESTROOM - FBC | | | 404.2.4 |
|