Notes
Date Text
2023-03-21 16:29:44THE MECHANICAL EQUIPMENT SIZING CALCULATIONS LIST A
 TOTAL LOAD FOR THE DOG GROOMING AHU AS 44,349 BTUS AND
 A TOTAL LOAD FOR THE OA COND AS 21.484 BTUS. THE
 MECHANICAL DRAWING SI SPECIFYING A 5-TON AND A 4-TON
 UNITS. THESE DOCUMENTS SHOULD REFLECT EACH OTHER.
 PROVIDE A CORRECTED DESIGN FOR THIS DOG GROOMING
 FACILITY. FEC C403.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  