| Date |
Text |
| 2023-01-12 15:11:26 | 3RD REVIEW FMC |
| | PERMIT: 22100216 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ADDRESS THE COMMENT BELOW FROM PREVIOUS REVIEW |
| | CYCLE: |
| | THE LIKE FOR LIKE DOCUMENT DOES NOT SHOW THIS TO BE A |
| | LIKE FOR LIKE. A GOOGLE MAPS SEARCH INDICATES THE |
| | BUILDINGS IN THAT AREA TO HAVE RTUS. PROVIDE THE |
| | MECHANICAL SIZING CALCULATIONS REQUIRED FOR THIS |
| | PROJECT ALONG WITH THE OUTDOOR AIR CALCULATIONS FOR THE |
| | USE OF THIS TENANT SPACE. FBC 107.3.5 |
| | |
| | 2) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON EACH |
| | OCCUPANCY CLASSIFICATION THAT MOST CLOSELY RESEMBLES |
| | THE USE IN THIS TENANT SPACE FROM TABLE 403.3.1.1. DOG |
| | GROOMING IS NOT LISTED AS AN OCCUPANCY CLASSIFICATION, |
| | BUT PET SHOPS- ANIMAL AREAS IS LISTED. THE OUTDOOR AIR |
| | CALCULATION SUBMITTED LISTS 5 PEOPLE IN THE DOG |
| | GROOMING AREA, THE TABLE LISTS THE MINIMUM PEOPLE AS |
| | 10. THE CALCULATION SHOW HAVE THE CORRECT PEOPLE COUNT |
| | THE CALCULATIONS AND DRAWINGS SUBMITTED DOES NOT SHOW |
| | THE CORRECT AMOUNT EXHAUST AIR CALCULATIONS. SHOW THE |
| | CORRECTED EXHAUST IN THE CALCULATIONS AND SHOW THE |
| | EXHAUST DESIGN ON THE DRAWINGS. PROVIDE THE INFORMATION |
| | FOR THE EXHAUST FANS. AND THE NEW MECHANICAL UNITS ON |
| | AN EQUIPMENT SCHEDULE. SHOW THE LOCATION OF THE |
| | CONDENSING UNIT. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |