Plan Review Notes
Plan Review Notes For Permit 22100200
Permit Number 22100200
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-11-02 16:09:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF EXTERIOR WORK ON A HIGH
 RISE BUILDING; HOWEVER, THE IS NO INDICATION OF
 PROTECTION FROM FALLING DEBRIS AROUND THE BUILDING(S)
 AND/OR PROTECTION OF EXIT TRAVEL PATHS.
  
 WITHIN THE SCOPE OF WORK THERE ARE INDICATIONS OF
 SCAFFOLDING, BOOM LIFTS, ETC...
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE REVIEW AND PROVIDE A
 LIFE SAFETY SHEET THAT INCLUDES PEDESTRIAN PROTECTION
 AROUND THE BUILDING AND SPECIFICALLY THE EXIT TRAVEL
 PATHS OR BLOCKED EXITS FROM THE BUILDING AND PROPOSED
 ALTERNATE ROUTING.
  
 SHOULD NO PROTECTION BE REQUIRED PLEASE PROVIDE A
 DETAILED NARRATIVE AND/OR PLAN SHEETS EXPLAINING WHY
 PROTECTION IS NOT REQUIRED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  