| Plan Review Notes For Permit 22100182 |
| Permit Number |
22100182 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-16 15:13:15 | RAILING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) BUILDING PERMIT APPLICATION SAYS HAND RAILS TO HANDI | | | CAP RAMP - THE DRAWINGS DO NOT COMPLY WITH HAND RAIL | | | REQUIREMENTS - FBC A 505 | | | | | | 2) NEED A BETTER SITE PLAN SHOWING THE LOCATION OF THE | | | PROPOSED RAILING. | | | | | | 3) HANDRAILS OR GUARD RAILS - PLEASE CLARIFY | | | | | | 4) FOR A GUARD RAIL - PLEASE SHOW THE PROPOSED HEIGHT. | | | FBC 1015.3 | | | | | | 5) THE SIGNED AND SEALED CALCULATIONS PROVIDED NEED TO | | | BE SIGNED DIGITALLY/ELECTRONICALLY BY THE DESIGNER TO | | | BE USED IN PROJECTDOX. |
|