2023-04-21 15:01:472ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100178
 4/21/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #1 & #11 ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET SP.003 & SP.620: REFER TO SEC.
 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION
 ON THE PLAN.
 A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT
 OCCUPANTS OF THE FACILITY.
 B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED.
  
 SHEETS SP.001: PLEASE CORRECT THE CALCULATIONS SO THEY
 CLEARLY INDICATE (TRANSIENT UNITS- 5 BATHERS PER
 TRANSIENT UNIT), AND (NON-TRANSIENT UNITS- 7 BATHERS
 PER TRANSIENT UNIT)- SEC. 454.1.1.1 FBC B. CORRECT THE
 MIAMI LOCATION TO WEST PALM BEACH.
  
 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING
 SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 &
 608.16 FBC P.
  
 SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
 PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  