| 2023-04-21 15:31:30 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22100178 |
| | 4/21/23 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS |
| | AND NOTE GAS CAN BE SUBMITTED AS A REVISION TO THE |
| | MASTER PLAN UNDER PERMIT 18100540. IF THIS OPTION IS |
| | CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS |
| | AND PERFORM THE REVIEW UNDER THE REVISION SUBMITTAL. |
| | |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEETS P.700: THE RISER BRANCH THAT |
| | CORRELATES TO KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON |
| | THE DRAWING. PLEASE PROVIDE A COMPLETE GAS RISER |
| | DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING |
| | INVOLVED WITH SUPPLYING THE GAS HEATER AND OTHER |
| | APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC |
| | CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE: |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND |
| | EQUIPMENT BTU LOADS. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | G) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | H) PIPE SIZING TABLES. |
| | |
| | THE RISER IS INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE |
| | LOW PRESSURE PIPING SYSTEM FROM THE REGULATORS TO THE |
| | POOL HEATERS. A COMPLETE RISER PER COMMENT #1 ABOVE IS |
| | REQUIRED. |
| | |
| | 5) FAILED. P.509: SHOW THE GAS VENT PIPING RUN AND |
| | TERMINATION LOCATION FROM THE EQUIPMENT ROOM BY |
| | GRIDLINES 10 & K- SEC. 410.3 FBC FG. |
| | |
| | THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET |
| | P.105C WHICH WAS NOT UPLOADED FOR REVIEW. |
| | |
| | 6) FAILED. P.509: PLEASE SUBMIT SHEET P.804 THAT |
| | CONTAINS THE GAS MONITORING AND DETECTING DETAILS |
| | CALLED OUT ON THE PLAN- SEC. 107.2.1 WPB. |
| | |
| | THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET |
| | P.804 WHICH WAS NOT UPLOADED FOR REVIEW. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |