Plan Review Notes
Plan Review Notes For Permit 22100178
Permit Number 22100178
Review Stop G
Sequence Number 2
Notes
Date Text
2023-04-21 15:31:302ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100178
 4/21/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE COMMENTS
 AND NOTE GAS CAN BE SUBMITTED AS A REVISION TO THE
 MASTER PLAN UNDER PERMIT 18100540. IF THIS OPTION IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE REVISION SUBMITTAL.
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEETS P.700: THE RISER BRANCH THAT
 CORRELATES TO KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON
 THE DRAWING. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 INVOLVED WITH SUPPLYING THE GAS HEATER AND OTHER
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 THE RISER IS INCOMPLETE BECAUSE IT DOES NOT INCLUDE THE
 LOW PRESSURE PIPING SYSTEM FROM THE REGULATORS TO THE
 POOL HEATERS. A COMPLETE RISER PER COMMENT #1 ABOVE IS
 REQUIRED.
  
 5) FAILED. P.509: SHOW THE GAS VENT PIPING RUN AND
 TERMINATION LOCATION FROM THE EQUIPMENT ROOM BY
 GRIDLINES 10 & K- SEC. 410.3 FBC FG.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.105C WHICH WAS NOT UPLOADED FOR REVIEW.
  
 6) FAILED. P.509: PLEASE SUBMIT SHEET P.804 THAT
 CONTAINS THE GAS MONITORING AND DETECTING DETAILS
 CALLED OUT ON THE PLAN- SEC. 107.2.1 WPB.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE REFERENCES SHEET
 P.804 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]