Plan Review Notes
Plan Review Notes For Permit 22100178
Permit Number 22100178
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-08 16:14:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100178
 11/8/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. BASED ON THE PERMIT
 APPLICATION PLEASE NOTE THE FOLLOWING COMMENTS ARE FOR
 THE HOTEL POOL ONLY WITH THE EXCEPTION OF COMMENT #1
 WHICH INCLUDES THE SPA.
  
 1) SHEETS SP.001 & A1.108: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH
 TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC.
 454.1.8.1 FBC B. THE FLOOR PLAN APPEARS TO SHOW THE
 BATHROOMS ADJACENT TO THE POOL DECK WILL ALSO BE USED
 BY OCCUPANTS OF THE OUTDOOR BAR. PLEASE SEE THE
 EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF APPLICABLE
 THEN THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE
 DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE
 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE
 THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE
 BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO
 CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE.
 PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS-
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SECS. 454.1.6.1.1 & 454.1.6.1.3: CONFIRM WITH
 DETAILS AND/OR NOTES THAT EACH BATHROOM CONTAINS A
 DIAPER CHANGING STATION AND A FLOOR DRAIN.
 C) SEC. 454.1.6.1.2: THE RESTROOMS ARE DO NOT APPEAR TO
 BE VISIBLE FROM ALL PORTIONS OF THE DECK. SHOW THE
 LOCATIONS OF DIRECTIONAL SIGNS FOR THE BATHROOM.
  
 2) SHEETS SP.100 & SP.120: THE PLANS SHOW ONLY TWO
 4-INCH GUTTER DRAINS. PLEASE SHOW THE LOCATIONS AND
 DIAMETERS OF ALL GUTTER DRAINS, AND NOTE THE SPACINGS
 BETWEEN DRAINS SHALL NOT EXCEED 10 FT. FOR 2-INCH
 DRAINS OR 15 FT. FOR 2-1/2 INCH UNLESS HYDRAULICALLY
 JUSTIFIED BY THE ENGINEER- SEC. 454.1.6.5.3.1 FBC B.
 A) PLEASE SHOW ALL GUTTER LOCATIONS ALONG THE PERIMETER
 OF THE POOL- SEC. 454.1.6.5.3.1 FBC B.
 B) SP.110 DETAIL 8: THE GUTTER DOES NOT APPEAR TO BE
 EITHER AN OPEN OR RECESSED TYPE AS REQUIRED BY SEC.
 454.1.6.5.3.1.2 FBC B. PLEASE PROVIDE MORE INFORMATION
 ABOUT THE DESIGN.
  
 3) SP.120: PLEASE PROVIDE TDH CALCULATIONS FOR PUMP
 SIZING- SEC. 454.1.6.5.4 FBC B.
  
 4) SP.120: PLEASE SHOW THE FLOOR INLET SPACINGS BETWEEN
 ADJACENT INLETS AND ADJACENT WALLS- SEC. 454.1.6.5.9.2
 FBC B.
  
 5) SP.130 & SP.730: PROVIDE A BACKFLOW PREVENTER FOR
 THE WATER SUPPLY LINE TO THE COLLECTOR TANK, AND
 INCLUDE AN EQUIPMENT SCHEDULE- SEC. 608.3 FBC P & SEC.
 454.1.6.3 FBC B.
  
 6) SP.700: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAIN GRATE AND SUMP SHOWING COMPLIANCE
 WITH SEC. 454.1.6.5.10.2 AND ANSI/APSP 16. PLEASE
 PROVIDE A NOTE AND/OR DETAIL ON THE PLAN INDICATING THE
 MAXIMUM VELOCITY OF WATER PASSING THROUGH THE OPENINGS
 DOES NOT EXCEED 11/2 FEET PER SECOND AT 100 PERCENT OF
 THE DESIGN RECIRCULATION FLOW. PLEASE NOTE THE SPECS
 MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH SEC.
 107.3.4.1 WPB.
  
 7) SP.120 & SP.700: THE PIPING PLANS SHOW POOL
 WASTEWATER DRAINING INTO THE SANITARY SYSTEM WHICH IS
 PROHIBITED- SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE
 DRAWINGS ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING
 INTO THE STORM. PLEASE REVIEW THE FOLLOWING INFORMATION
 AND REVISE THE PLAN ACCORDINGLY.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 8) SP.120, SP.700, SP.730 & P.509: THE EMERGENCY SHOWER
 AND EYEWASH STATIONS SHALL CONFORM TO ISEA Z358.1.
 SUBMIT MANUFACTURER' S SPECIFICATIONS TO VERIFY
 COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. PLEASE NOTE
 THE SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE
 WITH SEC. 107.3.4.1 WPB.
  
 9) SP.100 & SP.120: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL LIFT SHOWING COMPLIANCE
 WITH SECS. 1009.1- 1009.2.9 FBC ACC. PLEASE NOTE THE
 SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH
 SEC. 107.3.4.1 WPB.
  
 10) SP.100: PLEASE CLARIFY IF THE SLOPED ENTRY FOR THE
 POOL IS INTENDED TO MEET COMPLIANCE WITH SECS. 242.2 &
 1009.3 FBC ACC BECAUSE THE CURRENT PLAN SHOWS
 NON-COMPLIANCE WITH SECS. 1009.3.2 & 1009.3 FBC ACC-
 1009.3.2 SUBMERGED DEPTH.
 SLOPED ENTRIES SHALL EXTEND TO A DEPTH OF 24 INCHES
 MINIMUM AND 30 INCHES (760 MM) MAXIMUM BELOW THE
 STATIONARY WATER LEVEL. WHERE LANDINGS ARE REQUIRED BY
 405.7, AT LEAST ONE LANDING SHALL BE LOCATED 24 INCHES
 MINIMUM AND 30 INCHES MAXIMUM BELOW THE STATIONARY
 WATER LEVEL.
 1009 1009.3.3 HANDRAILS.
 AT LEAST TWO HANDRAILS COMPLYING WITH 505 SHALL BE
 PROVIDED ON THE SLOPED ENTRY. THE CLEAR WIDTH BETWEEN
 REQUIRED HANDRAILS SHALL BE 33 INCHES MINIMUM AND 38
 INCHES MAXIMUM.
  
 11) P.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 12) SP.700: PROVIDE A POOL EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  