Plan Review Notes
Plan Review Notes For Permit 22100178
Permit Number 22100178
Review Stop G
Sequence Number 1
Notes
Date Text
2022-11-08 16:50:521ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100178
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS
 FOR THE HOTEL POOL WHICH HAS A GAS-FIRED POOL HEATER,
 HOWEVER SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL
 HEATERS FOR THE INDOOR POOL AND SPAS THE APPLICANTS
 SHOULD CONSIDER SUBMITTING A SEPARATE PERMIT
 APPLICATION FOR GAS THAT INCLUDES ALL THE GAS WORK
 RELATING TO THE POOLS AND SPAS. IF A SEPARATE PERMIT IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE SEPARATE PERMIT.
 PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE
 QUESTIONS..
  
 1) SHEETS SP.120, SP.700, P.509, P.700: THE RISER
 BRANCH THAT CORRELATES TO KEYNOTE 1 ON SHEET P.700 DOES
 NOT APPEAR TO BE SHOWN ON THE DRAWING. PLEASE PROVIDE A
 COMPLETE GAS RISER DRAWING THAT INCLUDES ALL NEW AND
 EXISTING GAS PIPING SUPPLYING THE NEW POOL HEATER AND
 APPLIANCES- SECTIONS 401.3 & 401.4 FBC FG. REFER TO FBC
 CHAPTER 4 FUEL FBC- THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) SP.120, SP.700, P.509, P.700: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG.
  
 3) SP.120, SP.700, P.509, P.700: INDICATE HOW
 COMBUSTION AIR WILL BE PROVIDED TO THE HEATER AND SHOW
 CALCULATIONS FOR INDOOR AIR IF APPLICABLE- SEC. 304.1
 FBC FG.
  
 4) SP.120, SP.700, P.509, P.700: PROVIDE A VENTING PLAN
 FOR THE HEATER- SEC. 503.1 FBC FG.
  
 5) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THE
 EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB.
  
 6) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION
 LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K-
 SEC. 410.3 FBC FG.
  
 7) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE
 GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE
 PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  