Plan Review Notes
Plan Review Notes For Permit 22100177
Permit Number 22100177
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-16 08:53:551ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100177
 11/16/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THE FOLLOWING
 COMMENTS WITH THE EXCEPTION OF COMMENT #1 ARE INTENDED
 FOR THE SPA ONLY
  
 1) SHEETS SP.001 & A1.108: PROVIDE PLUMBING FIXTURE
 CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH
 TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC.
 454.1.8.1 FBC B. THE FLOOR PLAN APPEARS TO SHOW THE
 BATHROOMS ADJACENT TO THE POOL DECK WILL ALSO BE USED
 BY OCCUPANTS OF THE OUTDOOR BAR. PLEASE SEE THE
 EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF APPLICABLE
 THEN THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE
 DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE
 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE
 THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE
 BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO
 CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE.
 PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS-
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SECS. 454.1.6.1.1 & 454.1.6.1.3: CONFIRM WITH
 DETAILS AND/OR NOTES THAT EACH BATHROOM CONTAINS A
 DIAPER CHANGING STATION AND A FLOOR DRAIN.
 C) SEC. 454.1.6.1.2: THE RESTROOMS ARE DO NOT APPEAR TO
 BE VISIBLE FROM ALL PORTIONS OF THE DECK. SHOW THE
 LOCATIONS OF DIRECTIONAL SIGNS FOR THE BATHROOM
 2) SP.210 DETAIL 7: SHOW THE WALL INLET LOCATION IS A
 MINIMUM OF 12-INCHES BELOW THE NORMAL OPERATING WATER
 LEVEL- SECS. 454.1.8.1 & 454.1.6.5.9 FBC B.
  
 3) SP.220 & SP.730: PLEASE PROVIDE TDH CALCULATIONS FOR
 PUMP SIZING- SEC. 454.1.8.1 454.1.6.5.4 FBC B.
  
 4) SP.220: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN
 EQUIPMENT SCHEDULE- SEC. 608.3 & 608.16 FBC P & SEC.
 454.1.6.3 FBC B.
  
 5) SP.220: THE PIPING PLANS SHOW SPA WASTEWATER
 DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED-
 SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS
 ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE
 STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND
 REVISE THE PLAN ACCORDINGLY.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER' S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 6) SP.509 & SP.710: THE EMERGENCY SHOWER AND EYEWASH
 STATIONS SHALL CONFORM TO ISEA Z358.1. SUBMIT
 MANUFACTURER' S SPECIFICATIONS TO VERIFY COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
  
 7) SP.200: SUBMIT MANUFACTURER' S SPECIFICATIONS FOR
 THE SPA LIFT SHOWING COMPLIANCE WITH SECS. 1009.1-
 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS CAN BE A
 DEFERRED SUBMITTAL PER SEC. 107.3.4.1 WPB.
  
 8) SP.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 9) P.210: PLEASE NOTE- SEC. 454.1.8.15.
 IF A SPA IS EQUIPPED WITH AN EMERGENCY CUTOFF OR KILL
 SWITCH, IT SHALL INCLUDE PROVISIONS FOR A MINIMUM 80
 DECIBEL AUDIBLE ALARM NEAR THE SPA TO SOUND
 CONTINUOUSLY UNTIL DEACTIVATED WHEN SUCH DEVICE IS
 TRIGGERED. THE FOLLOWING ADDITIONAL RULE SIGN SHALL BE
 INSTALLED TO BE VISIBLE BY THE SPA WHICH READS "ALARM
 INDICATES SPA PUMPS OFF. DO NOT USE SPA WHEN ALARM
 SOUNDS UNTIL ADVISED OTHERWISE".
  
 10) SP.220: PROVIDE A SPA EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  