| Date |
Text |
| 2022-11-16 08:53:55 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100177 |
| | 11/16/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THE FOLLOWING |
| | COMMENTS WITH THE EXCEPTION OF COMMENT #1 ARE INTENDED |
| | FOR THE SPA ONLY |
| | |
| | 1) SHEETS SP.001 & A1.108: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH |
| | TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC. |
| | 454.1.8.1 FBC B. THE FLOOR PLAN APPEARS TO SHOW THE |
| | BATHROOMS ADJACENT TO THE POOL DECK WILL ALSO BE USED |
| | BY OCCUPANTS OF THE OUTDOOR BAR. PLEASE SEE THE |
| | EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF APPLICABLE |
| | THEN THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE |
| | DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE |
| | 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE |
| | THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE |
| | BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO |
| | CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE. |
| | PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| | SECTIONS- |
| | A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES |
| | THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE |
| | POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE |
| | TIMES THE AREA OF THE POOL SURFACE. |
| | B) SECS. 454.1.6.1.1 & 454.1.6.1.3: CONFIRM WITH |
| | DETAILS AND/OR NOTES THAT EACH BATHROOM CONTAINS A |
| | DIAPER CHANGING STATION AND A FLOOR DRAIN. |
| | C) SEC. 454.1.6.1.2: THE RESTROOMS ARE DO NOT APPEAR TO |
| | BE VISIBLE FROM ALL PORTIONS OF THE DECK. SHOW THE |
| | LOCATIONS OF DIRECTIONAL SIGNS FOR THE BATHROOM |
| | 2) SP.210 DETAIL 7: SHOW THE WALL INLET LOCATION IS A |
| | MINIMUM OF 12-INCHES BELOW THE NORMAL OPERATING WATER |
| | LEVEL- SECS. 454.1.8.1 & 454.1.6.5.9 FBC B. |
| | |
| | 3) SP.220 & SP.730: PLEASE PROVIDE TDH CALCULATIONS FOR |
| | PUMP SIZING- SEC. 454.1.8.1 454.1.6.5.4 FBC B. |
| | |
| | 4) SP.220: PROVIDE A BACKFLOW PREVENTER FOR THE WATER |
| | SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN |
| | EQUIPMENT SCHEDULE- SEC. 608.3 & 608.16 FBC P & SEC. |
| | 454.1.6.3 FBC B. |
| | |
| | 5) SP.220: THE PIPING PLANS SHOW SPA WASTEWATER |
| | DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED- |
| | SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS |
| | ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE |
| | STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND |
| | REVISE THE PLAN ACCORDINGLY. |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER' S |
| | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| | STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| | * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 6) SP.509 & SP.710: THE EMERGENCY SHOWER AND EYEWASH |
| | STATIONS SHALL CONFORM TO ISEA Z358.1. SUBMIT |
| | MANUFACTURER' S SPECIFICATIONS TO VERIFY COMPLIANCE. |
| | A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT, |
| | THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE |
| | CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE |
| | COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. |
| | |
| | 7) SP.200: SUBMIT MANUFACTURER' S SPECIFICATIONS FOR |
| | THE SPA LIFT SHOWING COMPLIANCE WITH SECS. 1009.1- |
| | 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS CAN BE A |
| | DEFERRED SUBMITTAL PER SEC. 107.3.4.1 WPB. |
| | |
| | 8) SP.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE |
| | PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE |
| | EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16 |
| | FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION |
| | BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM |
| | OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER. |
| | |
| | 9) P.210: PLEASE NOTE- SEC. 454.1.8.15. |
| | IF A SPA IS EQUIPPED WITH AN EMERGENCY CUTOFF OR KILL |
| | SWITCH, IT SHALL INCLUDE PROVISIONS FOR A MINIMUM 80 |
| | DECIBEL AUDIBLE ALARM NEAR THE SPA TO SOUND |
| | CONTINUOUSLY UNTIL DEACTIVATED WHEN SUCH DEVICE IS |
| | TRIGGERED. THE FOLLOWING ADDITIONAL RULE SIGN SHALL BE |
| | INSTALLED TO BE VISIBLE BY THE SPA WHICH READS "ALARM |
| | INDICATES SPA PUMPS OFF. DO NOT USE SPA WHEN ALARM |
| | SOUNDS UNTIL ADVISED OTHERWISE". |
| | |
| | 10) SP.220: PROVIDE A SPA EQUIPMENT SUBMITTAL PACKAGE |
| | THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN |
| | THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND |
| | RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT- |
| | SEC. 107.2.1 WPB. PLREASE NOTE ALL SUBMITTALS CAN BE |
| | DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC. |
| | 10.3.4.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |