| Plan Review Notes For Permit 22100177 |
| Permit Number |
22100177 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-12-14 16:27:54 | POOL SPA | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE MAXIMUM STEP RISER IS 10" - FBC 454.1.2.5.3 | | | | | | 2) DRAWING SP.001 SHOWS THE CODE VERSION USED FOR | | | DESIGN AS 2017 FBC - DRAWING 2.51 SHOWS THE 2014 FBC - | | | PLEASE SHOW THE CORRECT CODE VERSION. | | | | | | 3) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN | | | PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED | | | TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE). | | | |
|