Plan Review Notes
Plan Review Notes For Permit 22100175
Permit Number 22100175
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-30 10:27:401ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22100175
 11/30/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP.002: REFER TO SEC. 454.1.1.1 FBC B AND
 PROVIDE THE FOLLOWING INFORMATION ON THE PLAN.
 A) POOL IS FOR USE BY OCCUPANTS OF A TRANSIENT OR
 NON-TRANSIENT FACILITY.
 B) BATHING LOAD CALCULATION.
  
 2) SP.002: PLEASE LABEL THE BATHROOMS BY THE POOL AND
 SPA AS MEN'S AND WOMEN'S POOL AND SPA BATHROOMS AND
 PROVIDE FIXTURE CALCULATIONS IN ACCORDANCE WITH SECTION
 454.1.8.1 AND TABLE 454.1. 454.1.6.1.1. PROVIDE A
 SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES FOR MALE AND FEMALE USE.
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SEC. 454.1.6.1.3: CONFIRM WITH DETAILS AND/OR NOTES
 THAT EACH BATHROOM CONTAINS A FLOOR DRAIN.
 C) SEC. 454.1.6.1.4: SHOW THE LOCATIONS OF REQUIRED
 HOSE BIBS WITHIN 25 FT. OF EACH BATHROOM AND NOTE THAT
 EACH WILL BE EQUIPPED WITH A VACUUM BREAKER.
 D) SEC. 454.1.6.1.2: THE POOL AND SPA BATHROOMS DO NOT
 APPEAR TO BE VISIBLE FROM ALL PORTIONS OF THE DECK.
 SHOW THE LOCATIONS OF DIRECTIONAL SIGNS FOR THE
 BATHROOM.
  
 3) SP.310 DETAIL 6: SHOW THE WALL INLET LOCATION IS A
 MINIMUM OF 12-INCHES BELOW THE NORMAL OPERATING WATER
 LEVEL- SECS. 454.1.8.1 & 454.1.6.5.9 FBC B.
  
 5) SP.320 & SP.740: PLEASE PROVIDE TDH CALCULATIONS FOR
 PUMP SIZING- SEC. 454.1.8.1 454.1.6.5.4 FBC B.
  
 6) SP.320: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN
 EQUIPMENT SCHEDULE- SEC. 608.3 & 608.16 FBC P & SEC.
 454.1.6.3 FBC B.
  
 7) SP.320: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE MAIN DRAIN GRATES AND SUMPS SHOWING COMPLIANCE
 WITH SEC. 454.1.6.5.10.2 AND ANSI/APSP 16. PLEASE NOTE
 THE SPECS CAN BE A DEFERRED SUBMITTAL PER SEC.
 107.3.4.1 WPB.
  
 8) SP.320: THE PIPING PLANS SHOW POOL WASTEWATER
 DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED-
 SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS
 ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE
 STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND
 REVISE THE PLAN ACCORDINGLY.
  
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 9) P.509: THE EMERGENCY SHOWER AND EYEWASH STATIONS
 SHALL CONFORM TO ISEA Z358.1. SUBMIT MANUFACTURER' S
 SPECIFICATIONS TO VERIFY COMPLIANCE.
 A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT,
 THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE
 CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE
 COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P.
  
 10) SP.310: SUBMIT MANUFACTURER" S SPECIFICATIONS FOR
 THE POOL LIFT SHOWING COMPLIANCE WITH SECS. 1009.1-
 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS CAN BE A
 DEFERRED SUBMITTAL PER SEC. 107.3.4.1 WPB.
  
 11) P.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE
 PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE
 EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16
 FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
  
 12) SP.320: PROVIDE A POOL EQUIPMENT SUBMITTAL PACKAGE
 THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN
 THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLEASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  