| Plan Review Notes For Permit 22100154 |
| Permit Number |
22100154 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-04 12:45:34 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF | | | ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL | | | AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT - | | | THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL | | | PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF | | | TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING | | | ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. | | | FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE | | | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, | | | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, | | | MATERIALS, FASTENING REQUIREMENTS, FLASHING | | | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE | | | REQUIRED TO BE INSTALLED | | | | | | 2) THE PROVIDED PRODUCT APPROVALS IN PROJECTDOX WILL | | | NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING | | | DESIGNER OF RECORD. | | | | | | 3) DRAWING T-1.0 HAS A LIST OF DEFERRED SUBMITTALS - | | | THE ABOVE ITEMS CAN BE DEFERRED. FBC WPB 107.3.4.1 | | | | | | | | | | | | | | | | | | | | | |
|