| 2023-03-17 15:09:01 | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 22100154 | | | 3/17/23 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P2: THE NEW PLAN SHEET SHOWS THE GALVANIZED | | | METAL GAS PIPING TO RUN UNDERGROUND BELOW THE HOUSE | | | UNPROTECTED. PLEASE REFER TO SECS G2415.11.1- | | | G2415.11.4 FBC RES. AND INDICATE HOW THE PIPE WILL BE | | | PROTECTED AGAINST CORROSION. PLEASE NOTE ZINC COATING | | | SHALL NOT BE DEEMED ADEQUATE PROTECTION- SEC. | | | G2415.11.2. | | | | | | 2) P2: THE NEW PLAN SHEET DOES NOT PROVIDE VENTING | | | DETAILS FOR THE NEW GAS FIREPLACE. PLEASE PROVIDE A | | | VENTING DIAGRAM SHOWING THE TYPE AND SIZE OF VENT FLUE, | | | THE TOTAL VENT RUN AND TERMINATION LOCATION- SECS. | | | G2427.1, G2434.1, & G2435,1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|