| 2023-03-20 15:50:22 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) DOOR NUMBER 7 ENTRY TO THE BEDROOM WILL ALSO NEED TO |
| | MEET THE 29" CLEAR OPENING TO HAVE ACCESS TO THE |
| | BATHROOM INSIDE - FBC R320.1.1 ALL NEW SINGLE-FAMILY |
| | HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND |
| | TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED |
| | WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE |
| | PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT |
| | HAS A 29-INCH (737 MM) CLEAR OPENING. FBC 404.2.3 CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 2) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF |
| | ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL |
| | AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT - |
| | THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL |
| | PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF |
| | TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING |
| | ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. |
| | |
| | 3) MULTIPLE ROOF NOTES ON THE DRAWINGS SHOW SHINGLES |
| | FOR THE ROOF SYSTEM. |
| | |
| | 4) THE 2ND FLOOR BEDROOM #2 - THE WINDOWS DO NOT SEEM |
| | TO MEET THE EMERGENCY ESCAPE REQUIREMENT OF 5.7 SQUARE |
| | FEET - FBC R310.2.1 MINIMUM OPENING AREA. |
| | EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET |
| | CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530 |
| | M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS |
| | SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF |
| | THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE |
| | INSIDE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |