| 2023-02-27 13:48:12 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE - FBC |
| | R807.1 |
| | |
| | 2) FBC R320.1.1 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, |
| | TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT |
| | LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE |
| | PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE |
| | GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM) |
| | CLEAR OPENING. FBC 404.2.3 CLEAR OPENINGS OF DOORWAYS |
| | WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE |
| | OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| | DEGREES. |
| | |
| | 3) PLEASE SHOW THE STAIR HAND RAIL DETAILS - FBC |
| | R311.7.8 |
| | |
| | 4) PLEASE SHOW THE GUARD RAIL DETAILS - FBC R312.1 |
| | |
| | 5) PRODUCT APPROVAL PROVIDED FOR THE ROOF TILE - PLEASE |
| | CIRCLE THE ROOF TILE ATTACHMENT TYPE IN THE PRODUCT |
| | APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE |
| | ADHESIVE PRODUCT APPROVAL. |
| | |
| | 6) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB |
| | 107.3.4 |
| | |
| | 7) THE WINDOW SCHEDULE ON DRAWING A-5.0 SHOWS - DOUBLE |
| | HUNG WINDOWS, CASEMENT WINDOWS, PUSH OUT FRENCH |
| | CASEMENT WINDOWS - PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | ALL WINDOW TYPES SHOWN ON THE WINDOW SCHEDULE. |
| | |
| | 8) DRAWING C-1 DOES NOT SHOW AS DIGITALLY SIGNED IN |
| | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX |
| | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED |
| | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |