| Plan Review Notes For Permit 22100150 |
| Permit Number |
22100150 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-11-18 15:13:52 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SOIL REPORT AS NOTED ON THE | | | DRAWINGS. | | | | | | 2) PLEASE SHOW THE DOOR FROM THE GARAGE TO THE LIVING | | | SPACE TO COMPLY WITH FBC R302.5.1 OPENING PROTECTION. | | | OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM | | | USED FOR SLEEPING PURPOSES SHALL NOT BE PERMITTED. | | | OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL | | | BE EQUIPPED WITH SOLID WOOD DOORS NOT LESS THAN 13/8 | | | INCHES (35 MM) IN THICKNESS, SOLID OR HONEYCOMBCORE | | | STEEL DOORS NOT LESS THAN 13/8 INCHES (35 MM) THICK, OR | | | 20-MINUTE FIRE-RATED DOORS. | | | | | | 3) PLEASE PROVIDE COPIES OF THE PRODUCT APPROVALS | | | LISTED ON THE DRAWINGS. | | | | | | 4) THE DRAWINGS SHOW EXISTING WINDOWS TO BE REPLACED | | | WITH CASEMENT WINDOWS - PLEASE LIST THE CASEMENT WINDOW | | | PRODUCT APPROVAL NUMBERS ON THE DRAWINGS AND PROVIDE | | | COPIES OF THOSE PRODUCT APPROVALS. ALL PRODUCT | | | APPROVALS NEED TO BE LISTED ON THE DRAWINGS OR BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD FBC WPB 107.3.4 | | | |
|