| Plan Review Notes For Permit 22100137 |
| Permit Number |
22100137 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-17 11:25:17 | THE FOLLOWING COMMENTS WERE SUBMITTED BY LT. BRIAN | | | DOLAN, DIVISION OF FIRE PREVENTION, WEST PALM BEACH | | | FIRE RESCUE. | | | | | | 25.2.1.1 UNLESS PERMITTED BY 25.2.1.2 THROUGH 25.2.1.8, | | | ALL PIPING AND ATTACHED APPURTENANCES SUBJECTED TO | | | SYSTEM WORKING PRESSURE SHALL BE HYDROSTATICALLY TESTED | | | AT 200 PSI (13.8 BAR) AND SHALL MAINTAIN THAT PRESSURE | | | WITHOUT LOSS FOR 2 HOURS. | | | | | | 25.2.1.5 WHERE ADDITION OR MODIFICATION IS MADE TO AN | | | EXISTING SYSTEM AFFECTING MORE THAN 20 SPRINKLERS, THE | | | NEW PORTION SHALL BE ISOLATED AND TESTED AT NOT LESS | | | THAN 200 PSI (13.8 BAR) FOR 2 HOURS. | | | | | | PLEASE ENSURE THAT A MECHANICAL INSPECTION # 603 - FIRE | | | SPRINKLER PIPE IS CALLED IN WITH FIRE SPRINKLER #310 | | | ??? FIRE SPRINKLER HEAD AND # 311 - PRESSURE TEST | | | INSPECTIONS. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|