| Plan Review Notes For Permit 22100121 |
| Permit Number |
22100121 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-20 12:28:26 | FIRE REVIEW COMMENTS: | | | | | | (1) FOR CLARIFICATION, INDICATE THE DISTANCE IN FEET | | | FROM THE NEAREST FIRE HYDRANT TO THE FDC. | | | | | | NFPA 14, 6.4.5.4 | | | | | | (2) PROVIDE DETAILS ON THE OMISSION OF FIRE SPRINKLER | | | HEADS AT THE TOP OF THE ELEVATOR SHAFT AND THE ELEVATOR | | | MACHINE ROOM. | | | | | | NFPA 13, 8.15.5 | | | | | | (3) PROVIDE DETAIL ON THE OMISSION OF FIRE SPRINKLER | | | COVERAGE FOR THE ROOF TOP AMENITIES SPACE (PLACE OF | | | ASSEMBLY THAT WILL INCLUDE COMBUSTIBLE | | | MATERIALS/FURNITURE) ON LEVEL 8, AND THE PORTE COCHERE | | | AND DROP OFF CANOPY ON THE FIRST (GROUND) LEVEL. | | | | | | NFPA 13, 8.15.7 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|