| 2023-02-07 10:21:37 | 3RD REVIEW FMC |
| | PERMIT: 22100087 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IS THIS AN EXISTING I-2 OCCUPANCY? IF SO THE |
| | MECHANICAL DESIGN SHALL MEET THE REQUIREMENTS OF ASHRAE |
| | 170-2017. FMC 407 |
| | |
| | 2) IT IS UNCLEAR TO THIS REVIEWER AS TO WHEREIN THE |
| | BUILDING THIS MECHANICAL WORK WILL BE COMPLETED. LABEL |
| | THE ROOMS ON THE MECHANICAL SHEET TO MATCH THE ROOM THE |
| | WORK IS TO BE COMPLETED FROM THE A-202 DRAWING. |
| | |
| | 3) IS THIS A NEW ADDITION? IS IT A MECHANICAL CHANGE |
| | OUT? IS IT CREATING NEW ROOMS WITHIN AN EXISTING |
| | FOOTPRINT? PLEASE HELP ME TO UNDERSTAND THE SCOPE OF |
| | THIS PROJECT. |
| | |
| | 4) SHEET M-1.0: THE AHU IS SUPPLING AIR TO THE NEXT |
| | ROOM FROM WHERE THE AHU IS LOCATED. SHOW THE RETURN AIR |
| | PATH FROM THIS ROOM BACK TO THE AHU IN THE OTHER ROOM. |
| | FMC 601.6 |
| | |
| | 5) THE AHU MUST MEET THE NEW FEDERAL GUIDELINES FOR THE |
| | SEER2 RATINGS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |