2023-02-07 10:21:373RD REVIEW FMC
 PERMIT: 22100087
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IS THIS AN EXISTING I-2 OCCUPANCY? IF SO THE
 MECHANICAL DESIGN SHALL MEET THE REQUIREMENTS OF ASHRAE
 170-2017. FMC 407
  
 2) IT IS UNCLEAR TO THIS REVIEWER AS TO WHEREIN THE
 BUILDING THIS MECHANICAL WORK WILL BE COMPLETED. LABEL
 THE ROOMS ON THE MECHANICAL SHEET TO MATCH THE ROOM THE
 WORK IS TO BE COMPLETED FROM THE A-202 DRAWING.
  
 3) IS THIS A NEW ADDITION? IS IT A MECHANICAL CHANGE
 OUT? IS IT CREATING NEW ROOMS WITHIN AN EXISTING
 FOOTPRINT? PLEASE HELP ME TO UNDERSTAND THE SCOPE OF
 THIS PROJECT.
  
 4) SHEET M-1.0: THE AHU IS SUPPLING AIR TO THE NEXT
 ROOM FROM WHERE THE AHU IS LOCATED. SHOW THE RETURN AIR
 PATH FROM THIS ROOM BACK TO THE AHU IN THE OTHER ROOM.
 FMC 601.6
  
 5) THE AHU MUST MEET THE NEW FEDERAL GUIDELINES FOR THE
 SEER2 RATINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  