| Plan Review Notes For Permit 22100087 |
| Permit Number |
22100087 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-12-19 14:53:24 | ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE EXISTING TENANT SEPARATION HOURLY | | | FIRE RATING - FBC 708.1 | | | | | | 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND | | | DESIGN - FBC 1603.1.4 | | | | | | 3) THE ADDRESS ON THE DRAWINGS NEEDS TO MATCH THE | | | ADDRESS OF THE BUILDING. | | | | | | 4) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC | | | 602.1 | | | | | | 5) PLEASE LABEL THE ACCESSIBLE ROOMS - FBC 233.3.4.2 | | | ALTERATIONS TO INDIVIDUAL RESIDENTIAL DWELLING UNITS. | | | IN INDIVIDUAL RESIDENTIAL DWELLING UNITS, WHERE A | | | BATHROOM OR A KITCHEN IS SUBSTANTIALLY ALTERED, AND AT | | | LEAST ONE OTHER ROOM IS ALTERED, THE REQUIREMENTS OF | | | 233.3.1 SHALL APPLY TO THE ALTERED RESIDENTIAL DWELLING | | | UNITS UNTIL THE TOTAL NUMBER OF RESIDENTIAL DWELLING | | | UNITS COMPLIES WITH THE MINIMUM NUMBER REQUIRED BY | | | 233.3.1.1 AND 233.3.1.2. RESIDENTIAL DWELLING UNITS | | | REQUIRED TO COMPLY WITH 233.3.1.1 SHALL BE ON AN | | | ACCESSIBLE ROUTE AS REQUIRED BY 206. | | | | | | 6) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER SEAT | | | DIMENSION DETAILS FBC A 610.3 | | | | | | 7) ACCESSIBLE RESTROOM = PLEASE SHOW THE SHOWER GRAB | | | BAR DIMENSION DETAILS FBC A 609 | | | | | | 8) ACCESSIBLE BATHROOM = PLEASE SHOW ALL SHOWER DETAILS | | | - THRESHOLDS, CONTROLS, GRAB BARS ETC. - DIMENSIONS AND | | | LOCATIONS PER FBC 608 |
|