2022-11-18 10:29:59ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL LOCATIONS OF ALL ELECTRIC SERVICE
 EQUIPMENT AND OUTDOOR AIR CONDITIONING EQUIPMENT ON
 ELECTRICAL FLOOR PLAN. ENSURE INSTALLATION COMPLIES
 WITH NEC 110.26 CLEARANCE REQUIREMENTS AND RECEPTACLE
 LOCATION COMPLIANCE WITH NEC 210.63 AND 210.64
 2) PLEASE PROVIDE A RECEPETACLE AT BATH SINK IN MIDDLE
 AND ADA BATHROM UNITS AS COMPLY WITH NEC 210.60(B)
 3) PLEASE PROVIDE A NOTE STATING INSTALLATION WILL
 COMPLY WITH NEC 210.8 GFI PROTECTION AND 210.12(B) OR
 (C) ARC FAULT PROTECTION
 4) IT APPEARS THE WRONG PANEL SCHEDULE AND LOAD
 CALCULATION SHEETS WERE SUBMITTED. PLEASE PROVIDE THE
 CORRECT SHEETS. FBC 107.2 NEC 215.5
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  