Plan Review Notes
Plan Review Notes For Permit 22100033
Permit Number 22100033
Review Stop P
Sequence Number 2
Notes
Date Text
2023-04-18 12:08:422ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100033
 4/18/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET SP.003 & SP.520: REFER TO SEC.
 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION
 ON THE PLAN.
 A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT
 OCCUPANTS OF THE FACILITY.
 B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE RESPONSES REFERS TO
 SHEETS SP.001, SP.002 WHICH WERE NOT UPLOADED FOR
 REVIEW.
  
 2) FAILED. SHEETS SP.003 & A1.10: PROVIDE PLUMBING
 FIXTURE CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE
 WITH TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC.
 454.1.8.1 FBC B. THERE ARE MULTIPLE BATHROOMS ON THE
 FLOOR, BUT NONE DESIGNATED AS POOL BATHROOMS. PLEASE
 SEE THE EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF
 APPLICABLE THEN THE FIXTURE REQUIREMENT FOR THE
 BUILDING SHALL BE DETERMINED AND IF IT EXCEEDS THE
 REQUIREMENT IN TABLE 454.1.6.1 THEN THE BUILDING
 REQUIREMENT SHALL REGULATE THE FIXTURE COUNT, OTHERWISE
 THE FIXTURE COUNT SHALL BE BASED ON THE REQUIREMENT FOR
 THE POOL. UNDER NO CIRCUMSTANCES SHALL THE FIXTURE
 COUNTS BE CUMULATIVE.
 PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS-
 A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES
 THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE
 POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE
 TIMES THE AREA OF THE POOL SURFACE.
 B) SECS. 454.1.6.1.3: CONFIRM WITH DETAILS AND/OR NOTES
 THAT EACH BATHROOM CONTAINS A FLOOR DRAIN.
  
 THE DESIGN PROFESSIONAL'S NARRATIVE RESPONSES REFERS TO
 SHEETS SP.001, SP.002 WHICH WERE NOT UPLOADED FOR
 REVIEW.
  
 6) FAILED. SP.520: PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN GRATE AND SUMP
 SHOWING COMPLIANCE WITH SEC. 454.1.6.5.10.2 AND
 ANSI/APSP 16.
  
 THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE
 DEFERRED BY REQUEST.
  
 9) FAILED. SP.510: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL LIFT SHOWING COMPLIANCE
 WITH SECS. 1009.1- 1009.2.9 FBC ACC. PLEASE NOTE THE
 SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH
 SEC. 107.3.4.1 WPB.
  
 THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE
 DEFERRED BY REQUEST.
  
 10) FAILED. SP.520: PROVIDE A POOL EQUIPMENT SUBMITTAL
 PACKAGE THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS
 LISTED IN THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND
 RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT-
 SEC. 107.2.1 WPB. PLEASE NOTE ALL SUBMITTALS CAN BE
 DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC.
 10.3.4.1 WPB.
  
 THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE
 DEFERRED BY REQUEST.
  
 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING
 SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 &
 608.16 FBC P.
  
 SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION
 BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM
 OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER.
 PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  