| Date |
Text |
| 2023-04-18 12:08:42 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100033 |
| | 4/18/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS |
| | ARE LISTED BELOW WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SHEET SP.003 & SP.520: REFER TO SEC. |
| | 454.1.1.1 FBC B AND PROVIDE THE FOLLOWING INFORMATION |
| | ON THE PLAN. |
| | A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT |
| | OCCUPANTS OF THE FACILITY. |
| | B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED. |
| | |
| | THE DESIGN PROFESSIONAL'S NARRATIVE RESPONSES REFERS TO |
| | SHEETS SP.001, SP.002 WHICH WERE NOT UPLOADED FOR |
| | REVIEW. |
| | |
| | 2) FAILED. SHEETS SP.003 & A1.10: PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE |
| | WITH TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC. |
| | 454.1.8.1 FBC B. THERE ARE MULTIPLE BATHROOMS ON THE |
| | FLOOR, BUT NONE DESIGNATED AS POOL BATHROOMS. PLEASE |
| | SEE THE EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF |
| | APPLICABLE THEN THE FIXTURE REQUIREMENT FOR THE |
| | BUILDING SHALL BE DETERMINED AND IF IT EXCEEDS THE |
| | REQUIREMENT IN TABLE 454.1.6.1 THEN THE BUILDING |
| | REQUIREMENT SHALL REGULATE THE FIXTURE COUNT, OTHERWISE |
| | THE FIXTURE COUNT SHALL BE BASED ON THE REQUIREMENT FOR |
| | THE POOL. UNDER NO CIRCUMSTANCES SHALL THE FIXTURE |
| | COUNTS BE CUMULATIVE. |
| | PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| | SECTIONS- |
| | A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES |
| | THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE |
| | POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE |
| | TIMES THE AREA OF THE POOL SURFACE. |
| | B) SECS. 454.1.6.1.3: CONFIRM WITH DETAILS AND/OR NOTES |
| | THAT EACH BATHROOM CONTAINS A FLOOR DRAIN. |
| | |
| | THE DESIGN PROFESSIONAL'S NARRATIVE RESPONSES REFERS TO |
| | SHEETS SP.001, SP.002 WHICH WERE NOT UPLOADED FOR |
| | REVIEW. |
| | |
| | 6) FAILED. SP.520: PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE MAIN DRAIN GRATE AND SUMP |
| | SHOWING COMPLIANCE WITH SEC. 454.1.6.5.10.2 AND |
| | ANSI/APSP 16. |
| | |
| | THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE |
| | DEFERRED BY REQUEST. |
| | |
| | 9) FAILED. SP.510: SUBMIT MANUFACTURER' S |
| | SPECIFICATIONS FOR THE POOL LIFT SHOWING COMPLIANCE |
| | WITH SECS. 1009.1- 1009.2.9 FBC ACC. PLEASE NOTE THE |
| | SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE WITH |
| | SEC. 107.3.4.1 WPB. |
| | |
| | THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE |
| | DEFERRED BY REQUEST. |
| | |
| | 10) FAILED. SP.520: PROVIDE A POOL EQUIPMENT SUBMITTAL |
| | PACKAGE THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS |
| | LISTED IN THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND |
| | RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT- |
| | SEC. 107.2.1 WPB. PLEASE NOTE ALL SUBMITTALS CAN BE |
| | DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC. |
| | 10.3.4.1 WPB. |
| | |
| | THE SUBMITTALS WERE NOT UPLOADED HOWEVER THEY MAY BE |
| | DEFERRED BY REQUEST. |
| | |
| | 11) FAILED. P.509: PLEASE REMOVE THE NOTE REQUIRING |
| | SEPARATE PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND |
| | PROVIDE EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & |
| | 608.16 FBC P. |
| | |
| | SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION |
| | BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM |
| | OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER. |
| | PLEASE PROVIDE THE REQUESTED COMPLIANCE INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |