| 2022-11-16 12:50:08 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22100033 |
| | 11/16/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC RES- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. BASED ON THE PERMIT |
| | APPLICATION PLEASE NOTE THE FOLLOWING COMMENTS ARE FOR |
| | THE INDOOR POOL ONLY WITH THE EXCEPTION OF COMMENT #2 |
| | WHICH INCLUDES THE SPA. |
| | |
| | 1) SHEET SP.003 & SP.520: REFER TO SEC. 454.1.1.1 FBC B |
| | AND PROVIDE THE FOLLOWING INFORMATION ON THE PLAN. |
| | A) THE POOL IS FOR USE BY TRANSIENT OR NON-TRANSIENT |
| | OCCUPANTS OF THE FACILITY. |
| | B) CLARIFY HOW THE BATHING LOAD WAS CALCULATED. |
| | |
| | 2) SHEETS SP.003 & A1.10: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS FOR THE POOL AND SPA IN ACCORDANCE WITH |
| | TABLE 403.6 FBC P, AND TABLE 454.1.6.1, AND SEC. |
| | 454.1.8.1 FBC B. THERE ARE MULTIPLE BATHROOMS ON THE |
| | FLOOR, BUT NONE DESIGNATED AS POOL BATHROOMS. PLEASE |
| | SEE THE EXCEPTION UNDER SEC. 454.1.6.1.1. AND IF |
| | APPLICABLE THEN THE FIXTURE REQUIREMENT FOR THE |
| | BUILDING SHALL BE DETERMINED AND IF IT EXCEEDS THE |
| | REQUIREMENT IN TABLE 454.1.6.1 THEN THE BUILDING |
| | REQUIREMENT SHALL REGULATE THE FIXTURE COUNT, OTHERWISE |
| | THE FIXTURE COUNT SHALL BE BASED ON THE REQUIREMENT FOR |
| | THE POOL. UNDER NO CIRCUMSTANCES SHALL THE FIXTURE |
| | COUNTS BE CUMULATIVE. |
| | PLEASE ALSO SHOW COMPLIANCE WITH THE FOLLOWING CODE |
| | SECTIONS- |
| | A) SEC. 454.1.6.1.1: CONFIRM WITH DETAILS AND/OR NOTES |
| | THAT FIXTURE COUNT IS DEEMED TO BE ADEQUATE FOR THE |
| | POOL AND SPA AND POOL AND SPA DECK THAT IS UP TO THREE |
| | TIMES THE AREA OF THE POOL SURFACE. |
| | B) SECS. 454.1.6.1.3: CONFIRM WITH DETAILS AND/OR NOTES |
| | THAT EACH BATHROOM CONTAINS A FLOOR DRAIN. |
| | |
| | 3) SP.520: THE PLANS SHOW ONLY TWO 4-INCH GUTTER |
| | DRAINS. PLEASE SHOW THE LOCATIONS AND DIAMETERS OF ALL |
| | GUTTER DRAINS, AND NOTE THE SPACINGS BETWEEN DRAINS |
| | SHALL NOT EXCEED 10 FT. FOR 2-INCH DRAINS OR 15 FT. FOR |
| | 2-1/2 INCH UNLESS HYDRAULICALLY JUSTIFIED BY THE |
| | ENGINEER- SEC. 454.1.6.5.3.1 FBC B. |
| | A) PLEASE SHOW ALL GUTTER LOCATIONS ALONG THE PERIMETER |
| | OF THE POOL- SEC. 454.1.6.5.3.1 FBC B. |
| | 3) SP.750: PLEASE PROVIDE TDH CALCULATIONS FOR PUMP |
| | SIZING- SEC. 454.1.6.5.4 FBC B. |
| | |
| | 4) SP.520: PLEASE SHOW THE SPACINGS BETWEEN ADJACENT |
| | WALL INLETS AND ADJACENT WALLS- SEC. 454.1.6.5.9.2 FBC |
| | B. |
| | |
| | 5) SP.520: PROVIDE A BACKFLOW PREVENTER FOR THE WATER |
| | SUPPLY LINE TO THE COLLECTOR TANK, AND INCLUDE AN |
| | EQUIPMENT SCHEDULE- SEC. 608.3 FBC P & SEC. 454.1.6.3 |
| | FBC B. |
| | |
| | 6) SP.520: PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE MAIN DRAIN GRATE AND SUMP SHOWING COMPLIANCE |
| | WITH SEC. 454.1.6.5.10.2 AND ANSI/APSP 16. |
| | |
| | 7) SP.520: THE PIPING PLANS SHOW POOL WASTEWATER |
| | DRAINING INTO THE SANITARY SYSTEM WHICH IS PROHIBITED- |
| | SEC. 90-126 (5) WPB CODE OF ORDINANCES. THE DRAWINGS |
| | ALSO SHOW THE COLLECTOR TANK OVERFLOW DRAINING INTO THE |
| | STORM. PLEASE REVIEW THE FOLLOWING INFORMATION AND |
| | REVISE THE PLAN ACCORDINGLY. |
| | SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| | SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| | DEPARTMENT. |
| | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW |
| | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| | * THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| | TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| | INLET). |
| | * NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| | INLET TO DISCHARGE EFFLUENT. |
| | * WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| | ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| | * DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| | PROPERTY. |
| | * FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| | STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| | * FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| | 822-2062 OR [email protected]. |
| | |
| | 8) SP.520, SP.509: THE EMERGENCY SHOWER AND EYEWASH |
| | STATIONS SHALL CONFORM TO ISEA Z358.1. SUBMIT |
| | MANUFACTURER' S SPECIFICATIONS TO VERIFY COMPLIANCE. |
| | A) PLEASE NOTE IF HOT WATER IS SUPPLIED TO THE UNIT IT, |
| | THE TEMPERATURE OF THE WATER SUPPLY SHALL ONLY BE |
| | CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE |
| | COMPLYING WITH ASSE 1071- SEC. 411.3 FBC P. PLEASE NOTE |
| | THE SPECS MAY BE A DEFERRED SUBMITTAL IN COMPLIANCE |
| | WITH SEC. 107.3.4.1 WPB. |
| | |
| | 9) SP.510: SUBMIT MANUFACTURER' S SPECIFICATIONS FOR |
| | THE POOL LIFT SHOWING COMPLIANCE WITH SECS. 1009.1- |
| | 1009.2.9 FBC ACC. PLEASE NOTE THE SPECS MAY BE A |
| | DEFERRED SUBMITTAL IN COMPLIANCE WITH SEC. 107.3.4.1 |
| | WPB. |
| | |
| | 10) SP.520: PROVIDE A POOL EQUIPMENT SUBMITTAL PACKAGE |
| | THAT INCLUDES BUT IS NOT LIMITED TO THE ITEMS LISTED IN |
| | THE SCHEDULE UNDER THE PERIMETER OVERFLOW AND |
| | RECIRCULATION SYSTEM, AND THE FILTRATION EQUIPMENT- |
| | SEC. 107.2.1 WPB. PLEASE NOTE ALL SUBMITTALS CAN BE |
| | DEFERRED AND PLACED ON SITE AT TIME OF INSPECTION- SEC. |
| | 10.3.4.1 WPB. |
| | |
| | 11) P.509: PLEASE REMOVE THE NOTE REQUIRING SEPARATE |
| | PERMITS FOR THE RPZ BACKFLOW PREVENTERS AND PROVIDE |
| | EQUIPMENT SCHEDULES ON THE PLAN- SEC. 608.3 & 608.16 |
| | FBC P. SEPARATE PERMITS ARE NOT REQUIRED FOR ISOLATION |
| | BACKFLOW DEVICES INSTALLED ON SUPPLY LINES DOWNSTREAM |
| | OF THE MAIN POTABLE WATER SERVICE BACKFLOW PREVENTER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |