| 2022-11-16 13:11:07 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22100033 |
| | 11/16/22 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS |
| | FOR THE INDOOR POOL WHICH HAS A GAS-FIRED POOL HEATER, |
| | HOWEVER SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL |
| | HEATERS FOR THE HOTEL POOL AND SPAS THE APPLICANTS |
| | SHOULD CONSIDER SUBMITTING A SEPARATE PERMIT |
| | APPLICATION FOR GAS THAT INCLUDES ALL THE GAS WORK |
| | RELATING TO THE POOLS AND SPAS. IF A SEPARATE PERMIT IS |
| | CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS |
| | AND PERFORM THE REVIEW UNDER THE SEPARATE PERMIT. |
| | PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE |
| | QUESTIONS.. |
| | |
| | 1) SHEETS P.700: THE RISER BRANCH THAT CORRELATES TO |
| | KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON THE DRAWING. |
| | PLEASE PROVIDE A COMPLETE GAS RISER DRAWING THAT |
| | INCLUDES ALL NEW AND EXISTING GAS PIPING INVOLVED WITH |
| | SUPPLYING THE GAS HEATER AND OTHER APPLIANCES- SECTIONS |
| | 401.3 & 401.4 FBC FG. REFER TO FBC CHAPTER 4 FUEL FBC- |
| | THE RISER SHALL INDICATE: |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND |
| | EQUIPMENT BTU LOADS. |
| | C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | F) OUTLET PRESSURES AT REGULATORS. |
| | G) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | H) PIPE SIZING TABLES. |
| | |
| | 2) SP.420, P.509, P.700: SUBMIT MANUFACTURER' S |
| | SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG. |
| | |
| | 3) M.207A: LABEL THE POOL HEATERS ON THE PLAN AND |
| | PROVIDE AN ENLARGED DIMENSIONED INTAKE AND EXHAUST DUCT |
| | DIAGRAM THAT SHOWS THE LENGTHS OF THE DUCT RUNS AND |
| | TERMINATION LOCATIONS WITH CLEARANCES- SEC. 617.1, |
| | 503.2.3 & 503.8 FGB FG. |
| | |
| | A) INDICATE HOW DUCTS WERE SIZED SUBMIT AND SUBMIT |
| | MANUIFACTURER'S SPECIFICATION FOR ALL COMPONENTS OF THE |
| | SYSTEM INCLUDING THE TERMINATION CAPS. |
| | |
| | B) SHOW THE TERMINATION LOCATION CLEARANCES TO OTHER |
| | EXHAUST OUTLETS AND AIR INTAKE OPENINGS. |
| | |
| | 4) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THESE |
| | EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB. |
| | |
| | 5) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION |
| | LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K- |
| | SEC. 410.3 FBC FG. |
| | |
| | 6) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE |
| | GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE |
| | PLAN- SEC. 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |