Plan Review Notes
Plan Review Notes For Permit 22100033
Permit Number 22100033
Review Stop G
Sequence Number 1
Notes
Date Text
2022-11-16 13:11:071ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100033
 11/16/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE PERMIT APPLICATION IS
 FOR THE INDOOR POOL WHICH HAS A GAS-FIRED POOL HEATER,
 HOWEVER SINCE SHEET P.509 & P.700 SHOWS MULTIPLE POOL
 HEATERS FOR THE HOTEL POOL AND SPAS THE APPLICANTS
 SHOULD CONSIDER SUBMITTING A SEPARATE PERMIT
 APPLICATION FOR GAS THAT INCLUDES ALL THE GAS WORK
 RELATING TO THE POOLS AND SPAS. IF A SEPARATE PERMIT IS
 CHOSEN I WILL PLACE AN "N" RESULT (NO REVIEW) FOR GAS
 AND PERFORM THE REVIEW UNDER THE SEPARATE PERMIT.
 PLEASE REVIEW THE COMMENTS AND CONTACT ME IF YOU HAVE
 QUESTIONS..
  
 1) SHEETS P.700: THE RISER BRANCH THAT CORRELATES TO
 KEYNOTE 1 DOES NOT APPEAR TO BE SHOWN ON THE DRAWING.
 PLEASE PROVIDE A COMPLETE GAS RISER DRAWING THAT
 INCLUDES ALL NEW AND EXISTING GAS PIPING INVOLVED WITH
 SUPPLYING THE GAS HEATER AND OTHER APPLIANCES- SECTIONS
 401.3 & 401.4 FBC FG. REFER TO FBC CHAPTER 4 FUEL FBC-
 THE RISER SHALL INDICATE:
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE AND
 EQUIPMENT BTU LOADS.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) SP.420, P.509, P.700: SUBMIT MANUFACTURER' S
 SPECIFICATIONS FOR THE POOL HEATER- SEC.617.1 FBC FG.
  
 3) M.207A: LABEL THE POOL HEATERS ON THE PLAN AND
 PROVIDE AN ENLARGED DIMENSIONED INTAKE AND EXHAUST DUCT
 DIAGRAM THAT SHOWS THE LENGTHS OF THE DUCT RUNS AND
 TERMINATION LOCATIONS WITH CLEARANCES- SEC. 617.1,
 503.2.3 & 503.8 FGB FG.
  
 A) INDICATE HOW DUCTS WERE SIZED SUBMIT AND SUBMIT
 MANUIFACTURER'S SPECIFICATION FOR ALL COMPONENTS OF THE
 SYSTEM INCLUDING THE TERMINATION CAPS.
  
 B) SHOW THE TERMINATION LOCATION CLEARANCES TO OTHER
 EXHAUST OUTLETS AND AIR INTAKE OPENINGS.
  
 4) P.509: PLEASE INDICATE WHICH FLOOR LEVELS THESE
 EQUIPMENT ROOMS ARE ON- SEC. 107.2.1 WPB.
  
 5) P.509: SHOW THE GAS VENT PIPING RUN AND TERMINATION
 LOCATION FROM THE EQUIPMENT ROOM BY GRIDLINES 10 & K-
 SEC. 410.3 FBC FG.
  
 6) P.509: PLEASE SUBMIT SHEET P.804 THAT CONTAINS THE
 GAS MONITORING AND DETECTING DETAILS CALLED OUT ON THE
 PLAN- SEC. 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]