| Plan Review Notes For Permit 22091344 |
| Permit Number |
22091344 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-24 16:02:12 | ELECTRIC REVIEW FAILED | | | 1) PLEASE DETAIL A GROUNDING ELECTRODE SYSTEM FOR THE | | | MAIN HOUSE PANEL AS PER NEC 250.32 | | | 2) PLEASE INCLUDE A NOTE ON THE PLANS DETAILING GUEST | | | HOUSE REQUIRES A SEPARATE PERMIT | | | 3) PLEASE INCLUDE GENERATOR, POOL WIRING REQUIRE A | | | SEPARATE PERMIT | | | 4) PLEASE DETAIL ALL REQUIRED OUTSIDE RECEPTACLES ON | | | MAIN HOUSE SECOND FLOOR AND GARAGE STRUCTURE, AS PER | | | NEC 210.52(E)(3) | | | 5) PLEASE CORRECT CONFLICTS BETWEEN RISER DIAGRAM AND | | | PANEL SCHEDULES FOR CONDUCTOR SIZE FEEDING PANEL A. | | | THIS CONDUCTOR SHOULD BE A MINIMUM SIZE OF #3 CU FOR A | | | 100 AMP PANEL. NEC 215.5 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|