Plan Review Notes
Plan Review Notes For Permit 22091340
Permit Number 22091340
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-10-05 09:47:15FIRE REVIEW COMMENTS:
  
 (1) WHAT WILL BE STORED INSIDE THE PROPOSED STORAGE
 BUILDING? NFPA 1, 1.14
  
 (2) WHAT IS THE DISTANCE OF THE PROPOSED STORAGE
 BUILDING EXTERIOR TO THE PROPERTY LINE? NFPA 80A, 4.3.7
  
 (3) WHAT IS THE DISTANCE OF THE PROPOSED STORAGE
 BUILDING TO THE MAIN BUILDING (EXTERIOR TO EXTERIOR
 DIMENSION)? NFPA 80A, 4.3.7
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  