Plan Review Notes
Plan Review Notes For Permit 22091326
Permit Number 22091326
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-04 14:33:561ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 1. PROVIDE A FLOOR PLAN WITH DEMENSIONS OF BATHROOM AND
 SHOWER STALL.
 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE
 WITH SECTIONS107.2.1 THROUGH 107.2.5
  
 2.SHOWER STALL DEMENSIONS
 FBC RES P2708.1GENERAL.
 SHOWER COMPARTMENTS SHALL HAVE NOT LESS THAN 900 SQUARE
 INCHES (0.6 M2) OF INTERIOR CROSS-SECTIONAL AREA.
 SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 30 INCHES
 (762 MM) IN MINIMUM DIMENSION MEASURED FROM THE
 FINISHED INTERIOR DIMENSION OF THE SHOWER COMPARTMENT,
 EXCLUSIVE OF FIXTURE VALVES, SHOWER HEADS, SOAP DISHES,
 AND SAFETY GRAB BARS OR RAILS.
  
 3.ACCESS/EGRESS
 P2708.1.1ACCESS.
 THE SHOWER COMPARTMENT ACCESS AND EGRESS OPENING SHALL
 HAVE A CLEAR AND UNOBSTRUCTED FINISHED WIDTH OF NOT
 LESS THAN 22 INCHES (559 MM).
  
 4.SHOWER WALL FINISH
 R702.4.1GENERAL.
 CERAMIC TILE.
 CERAMIC TILE SURFACES SHALL BE INSTALLED IN ACCORDANCE
 WITH ANSI A108.1, A108.4, A108.5, A108.6, A108.11,
 A118.1, A118.3, A136.1 AND A137.1.
 1210.2.3 SHOWERS.
 SHOWER COMPARTMENTS AND WALLS ABOVE BATHTUBS WITH
 INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A SMOOTH,
 NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72
 INCHES (1829 MM) ABOVE THE DRAIN INLET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.