Plan Review Notes
Plan Review Notes For Permit 22091294
Permit Number 22091294
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-07 09:01:491ST REVIEW FMC
 PERMIT: 22091294
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THE HOUSE. FEC
 R101.5.1.1.1
  
 2) THE ENERGY CALCULATIONS SUBMITTED FOR THE GARAGE AND
 GUEST HOUSE INDICATES THE CONDENSING UNIT IS A 2.55
 TONS 30,582 BTU???S. SHEET M-1 INDICATES THIS
 CONDENSING UNIT TO BE 24,000 BTU MAX. MAKE SURE THE
 DOCUMENTS SUBMITTED MATCH. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  