Plan Review Notes
Plan Review Notes For Permit 22091293
Permit Number 22091293
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-14 10:42:47ELECTRIC REVIEW FAILED
 1) PLEASE RESTATE OR REMOVE INACCURATE NOTE ON SHEET
 E-03 REGARDING NEC 225-30(B)
 FBC 107.2
 2) PLEASE DETAIL THE REQUIRED GROUNDING ELECTRODE
 SYSTEM FOR THE REMOTE STRUCTURE, PANEL A, AS PER NEC
 250.32
 3) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AT
 KITCHEN, FRONT, MASTER BEDROOM AND CABANA PORCHES OR
 DECKS AS PER NEC 210.52.(E)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  